3-7
IM 34M06H43-02E 2nd Edition : Sep.30, 2019-00
■
Attaching Modules in Intense Vibration Environments
If the module is used in intense vibration environments, fasten the module with a
screw. Use screws of type listed in the table below. Insert these screws into the
screw holes on top of the module and tighten them with a Phillips screwdriver.
Screw Required
M4-size binder screw 12 to 15 mm long
(Or 14 to 15 mm if fitted with a washer)
Figure 3.5.2 Tightening the Module
■
Depth Dimension of the Mounted Module
The depth from the back of the base module to the front of the FA Link H2 module is
89.9 mm. As cables with a connector are attached to the module, a depth that is
deep enough for the cables to be bent is required. Figure 3.5.3 shows the required
depth to install the FA Link H2 module.
*1: Note that the required depth differs depending on the thickness and hardness of the cables as well as the length of the
coating to be removed.
Figure 3.5.3 Required Depth to Install the Module
Module Name
D(mm)
d(mm)
FA Link H2 module
89.9
About
150
*1
D
d