
<12. Troubleshooting>
12-9
IM 11M12A01-02E 16th Edition : Mar. 19, 2020-00
(1) Breakage of the cold junction signal wires between the converter and the detector, or the
cable is not securely connected to the connecting terminals.
(2) The positive and negative poles of the cold junction signal wiring are shorted out in the
wiring extension or at the connection terminals.
(3) A failure of the cold junction temperature sensor located at the detector terminal block
occurred.
(4) A failure of the electrical circuits inside the converter occurred.
If “C.J.temperature” exceeds 150°C or falls below -20°C, the following can be considered.
• The temperature of the detector terminal block is out of the operating temperature range
(-20°C to 150°C).
• A failure of the cold junction temperature sensor located at the detector terminal block
occurred.
• A failure of the electrical circuits inside the converter occurred.
<Locating cause of failure and countermeasures>
Before proceeding to the following troubleshooting procedure, examine whether or not the
temperature of the detector terminal block is out of the operating temperature range.
The operating temperature range varies with the type of detector. If the detector terminal block
is out of its operating temperature range, take the measure to lower the temperature, such as
situating it so that it is not subjected to radiant heat.
The case where the Model ZR22 Detector is used:
(1) Stop the power to the converter.
(2) Remove the wiring from terminals 5 and 6 of the detector and measure the resistance
between these terminals. If the resistance value is out of the range of 1 to 1.6 kΩ, the cold
junction temperature sensor is considered to be faulty. Replace that temperature sensor
with a new one.
(3) If the resistance value is within the above range, the cold junction temperature sensor
seems to be normal. Check whether or not the cable is broken or shorted out, and whether
the cable is securely connected to the terminals. Also, check that the resistance of the wiring
between the converter and detector is 10 Ω or less.
(4) If there is no failure in the wiring, the electrical circuits inside the converter may possibly fail.
Contact the service personnel at Yokogawa.
The case where the Model ZO21D Detector is used:
(1) Without stopping the power to the converter, remove the wiring from terminals 5 and 6 of
the detector and measure the voltage between these terminals. If the voltage between the
terminals is out of the range of 0.4 to 0.7 V, the cold junction temperature sensor seems to
be faulty. Replace the cold junction temperature sensor.
(2) If the voltage between the terminals is within the above range, the cold junction temperature
sensor seems to be normal. Check whether or not the cable is broken or shorted out, and
whether the cable is securely connected to the terminals. Also, check that the resistance of
the wiring between the converter and detector is 10 Ω or less.
(3) If there is no failure in the wiring, the electrical circuits inside the converter may possibly fail.
Contact the service personnel at Yokogawa.
CAUTION
The operating temperature range of the Model ZO21D Detector is -10°C to 80°C (except for the
high temperature detector ZO21D-H). Since a cold junction temperature alarm for this analyzer
is not generated until the temperature exceeds 155°C, if the Model ZO21D Detector is used, be
careful in controlling the ambient temperature of the terminal block.
Summary of Contents for EXAxt ZR22G
Page 15: ...Blank Page...
Page 51: ...Blank Page...
Page 77: ...Blank Page...
Page 137: ...Blank Page...
Page 171: ...Blank Page...
Page 195: ...Blank Page...
Page 197: ......
Page 199: ......
Page 201: ......
Page 203: ......
Page 205: ......
Page 207: ......
Page 211: ...Blank Page...