5-2.3 Select monitor pulse type (optional)
Monitor pulse type is the feedback pulse signal output from drive to PLC.
If necessary, please choose from the following options.
・UP,DOWN output
・A,B output
Refer to the following table for spec. of the pulse type.
Setup method is described in [5-2.4 Setup of selected pulse type].
+ direction
- direction
3Mpps
Moving direction
Definition
Max output frequency
CN4-9
Wiring
CN4-10
CN4-11
CN4-12
(A、B)
DOWN
UP
3MHz max
UA_OUT-
DB_OUT-
Signal
A
B
750kHz max
+ direction
- direction
(UP、DOWN)
750kpps
Monitor pulse output type
5-2.2 Select command pulse type
Command pulse type is the kind of pulse command issued by PLC.
Please choose it from the following 3 options.
・PLS,SIGN input
・UP,DOWN (CW,CCW)input
・A,B input
Refer to the following table for the spec. of each type.
Setup method is described in [5-2.4 Setup of selected pulse type].
PUA_IN+
Max command
frequency
PUA_IN-
SDB_IN+
SDB_IN-
CN4-15
Wiring
CN4-16
CN4-17
CN4-18
Spec. of differential input
Spec. of open collector input
Definition
Signal
+ direction
- direction
2Mpps
SIGN
3μs min 3μs min
PLS
150ns min
Moving direction
200kpps
Min H level time:
+ direction
- direction
2Mpps
200kpps
DOWN
6μs min
UP
150ns min
Moving direction
+ direction
- direction
(A、B)
200kpps
500kpps
A
B
300ns min
PLS,SIGN input
UP,DOWN input
A,B input
Command pulse type
PLC
Drive
PLC
Drive
*)
*) Error occurs if drive detects the max command frequency.
5-4
Min H level time: