1. System Installation Requirements
1-12
TI 33Q01J10-01E
SEE
ALSO
For the level of corrosive gases permitted in an ordinary office, refer to “Guidelines for Installation Environment”
(TI 33Q01J20-01E).
The following table shows the installation environment standard for the occasion where devices
including PC or UPS are mounted in the console kit.
Table Installation Environment Standard Used When PC or UPS is Built in Console Kit
Item
Enclosed display style console assembly
Open display style console assembly
Temperature
The range including the console kit temperature
range and the installed device temperature ranges
(Subtract 5 °C from the upper limit) is the standard
for the installation environment.
The range including the console kit temperature
range and the installed device temperature ranges
is the standard for the installation environment.
Humidity
The range including the console kit humidity range and the installed device humidity ranges is the
standard for the installation environment.
Temperature
fluctuation
The console kit temperature fluctuation or the installed device temperature fluctuation whichever is
severer is the standard for the installation environment.
Power
source
For the voltage range and frequency, the range including the console kit range and the PC or UPS range
is the standard for the installation environment. For the distortion factor, peak value, and instantaneous
power failure, the console kit value or the PC or UPS value whichever is severer is the standard for the
installation environment.
Withstand
voltage
1500 V AC for 1 minutes for PC or UPS which has obtained IEC 60950-1-equivalent safety standard
(EN 60950-1, CSA C22.2 No.60950-1, UL 60950-1).
Note: Choose a PC or UPS which has obtained or conforms to the above safety standard.
Insulation
resistance
The console kit insulation resistance or the PC or UPS insulation resistance whichever is lower
Noise
The console kit value or the PC or UPS value whichever is lower
Note: Usually, PCs have obtained EN 55024 or equivalent as noise standard.
The EN 55024 standard defines the electrical field, magnetic field, and static electricity as follows:
Electrical field
3 V/m 80 to 1000 MHz
Magnetic field
1 A/m (AC) No standard for DC
Static electricity
4 kV or less (contact discharge), 8 kV or less (aerial discharge)
Vibration
The vibration characteristic depends on the specifications of the installed devices.
Dust,
corrosive gas
The console kit environmental specification or the PC or UPS environmental specification whichever is
severer is the standard for the installation environment.
Feb. 1, 2009-00