4. Installation Specifications
4-16
TI 33Q01J10-01E
Feb. 1, 2009-00
AFS30
, AFG30
/AFS40
, AFG40
/ANB10
/ANR10
Table Periodic Replacement Parts Having Defined Life Spans
Part
names
Part
numbers
Recommended
replacement
cycle
Used in:
Replacement
by user
Remarks
A
F
3
0
A
F
4
0
A
N
B
1
0
A
N
R
1
0
Aluminium
Electrolytic
Capacitor
(in power
supply unit)
(PW301)
8 years
X X
No
100 V AC
Average ambient temperature 40 °C or less
(PW302)
8 years
X X
No
220 V AC
Average ambient temperature 40 °C or less
(PW304)
8 years
X X
No
24 V DC
Average ambient temperature 40 °C or less
(PW481)
8 years
X X
No
100 V AC
Average ambient temperature 40 °C or less
(PW482)
8 years
X X
No
220 V AC
Average ambient temperature 40 °C or less
(PW484)
8 years
X X
No
24 V DC
Average ambient temperature 40 °C or less
Fan Unit
AIP601
4 years
X X
Yes
Air Filter
T9070CK
1 year
X
Yes
For nest fan. Wash every 3 months.
T9070CB
1 year
X
Yes
For door fan. Wash every 3 months.
Battery
Pack
S9400UK
S9765UK
3 years
X X
Yes
Average ambient temperature 30 °C or less
1.5 years
X X
Yes
Average ambient temperature 40 °C or less
9 months
X X
Yes
Average ambient temperature 50 °C or less
Fuse
S9580VK
3 years
X X
No
PW302
S9502VK
3 years
X X
No
PW301
S9504VK
3 years
X X
No
PW304, PW404
S9109VK
8 years
X X
No
PW481, PW482
A1546EF
8 years
X X
No
PW484
X:
Usage