1. System Installation Requirements
1-24
TI 33Q01J10-01E
Grounding with Other System
As far as possible, avoid mounting CS 3000 in contact with an other system. If this cannot be
avoided, either provide insulating sheets and separate grounding or insulate the other system
from the floor, and ground both CS 3000 and the other system via a common ground bar.
IMPORTANT
Do not install the following systems side-by-side with CS 3000:
• Systems using power supply voltages over 300 V AC.
• Systems with current consumption over 50 A.
• System containing high frequency sources.
G
Cabinet
G
100 ohms or less
F010405.ai
Ground bus
Insulating sheet
Insulating sheet
CS 3000
Other system
Insulating sheet material: PVC or PL-PEV Bakelite
Thickness:
5-10 mm
Figure Grounding Using Insulating Sheets
G
Cabinet
G
100 ohms or less
F010406.ai
Ground bus
Insulating sheet
CS 3000
Other system
Figure Grounding by Insulation from Floor