3. Cabling
3-101
TI 33Q01J10-01E
Terminator
Regarding EB401 and EB501, if one side of T-type connector is terminal, mount a terminator.
Two terminators are supplied with EB401.
Clamp Filter
Regarding EB401 and EB501, mount clamp filters to both side of T-type connector. If one of
the sides is terminal, mount a clamp filter to only the cable side. Two (four for dual-redundant)
clamp filters are supplied with the remote node. For EB401, use the clamp filter supplied with the
terminal remote node.
F030823.ai
Within 10 cm
Clamp Filter
Figure Clamp Filter
T-type connector
When the ER bus cable is connected, put the T-type connector between insulation sheets to
prevent it from touching other metals. The surfaces of the insulation sheets that come with the
T-type connector (2 sheets) are adhesive. The figure below shows how to attach them.
Place two pieces of insulation sheets so that the adhesive surfaces face the T-type connector
and sandwich the T-type connector between them.
Press the two pieces of insulation sheets together tightly with your fingers, making sure that the
sheets cover the metal part of the T-type connector.
F030824.ai
Insulation sheet
T-type connector
Figure Insulation Sheet
Feb. 1, 2009-00