9
-2
Standard Inverter Specifications
The standard Inverter specifications are listed by capacity in the following tables.
Specifications by Model
Specifications are given by model in the following tables.
200 V Class
* 1. The maximum applicable motor output is given for a standard 4-pole Yaskawa motor. When selecting the actual motor and Inverter, be sure that the Inverter's
rated current is applicable for the motor's rated current.
* 2. The voltage of the cooling fan for 200 V Class Inverters of 30 kW is three-phase, 200, 208, or 220 V at 50 Hz or 200, 208, 220, or 230 V at 60 Hz.
* 3. A 3-wire transformer is required on the power supply for 12-phase rectification.
Table 9.1 200 V Class Inverters
Model Number CIMR-G7A
20P4
20P7
21P5
22P2
23P7
25P5
27P5
2011
2015
2018
2022
2030
2037
2045
2055
2075
2090
2110
Max. applicable motor output
(kW)
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
Rated input current (A)
3.8
7.2
9.6
14.4
22
32
40
59
79
88
106
143
176
201
246
330
394
457
Rated output capacity
(kVA)
1.2
2.3
3.0
4.6
6.9
10
13
19
25
30
37
50
61
70
85
110
140
160
Rated output current (A)
3.2
6
8
12
18
27
34
49
66
80
96
130
160
183
224
300
358
415
Max. output voltage (V)
3-phase; 200, 208, 220, 230, or 240 VAC
(Proportional to input voltage.)
Max. output frequency
(Hz)
Frequencies supported up to 400 Hz using constant setting
Rated voltage (V)
Rated frequency (Hz)
3-phase, 200/208/220/230/240 VAC, 50/60 Hz
*2
Allowable voltage fluctua-
tion
+ 10%, - 15%
Allowable frequency fluc-
tuation
±5%
Measures for
power supply
harmonics
DC reactor
Optional
Built in
12-phase rec-
tification
Not possible
Possible
*3
O
utpu
t r
at
ings
P
ower
s
upp
ly c
har
act
er
ist
ics