User Constant Tables
5-
35
* 1. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
* 2. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V Class Inverter for 0.4 kW is given.
For the motor no-load current, set E2-03 to a value less than that of E2-01.
* 3. The setting range depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given. The upper limit depends on the setting of
E2-01.
* 4. The same capacity as that of the Inverter will be set if the constants are initialized.
E2-06
Motor leak
inductance
Sets the voltage drop due to
motor leakage inductance as a
percentage of the motor rated
voltage.
This constant is automatically
set during autotuning.
0.0 to
40.0
18.2%
*1
No
No
No
A
A
A
313H
6-117
Leak Induc-
tance
E2-07
Motor iron
saturation
coefficient 1
Sets the motor iron saturation
coefficient at 50% of mag-
netic flux.
This constant is automatically
set during autotuning.
0.00 to
0.50
0.50
No
No
No
A
A
A
314H
6-117
Saturation
Comp1
E2-08
Motor iron
saturation
coefficient 2
Sets the motor iron saturation
coefficient at 75% of mag-
netic flux.
This constant is automatically
set during autotuning.
0.00 to
0.75
0.75
No
No
No
A
A
A
315H
6-117
Saturation
Comp2
E2-09
Motor
mechanical
loss
Sets motor mechanical loss as
a percentage of motor rated
output (W).
Usually setting is not neces-
sary.
Adjust in the following cir-
cumstances:
•
When torque loss is large
due to motor bearing.
•
When the torque loss in the
pump or fan is large.
The set mechanical loss will
compensate for torque.
0.0 to
10.0
0.0
No
No
No
No
A
A
316H
-
Mechanical
Loss
A
E2-10
Motor iron
loss for
torque com-
pensation
Sets motor iron loss in W
units.
0 to
65535
14 W
*1
No
A
A
No
No
No
317H
6-118
Tcomp Iron
Loss
E2-11
Motor rated
output
Set the rated output of the
motor in units of 0.01 kW.
This constant is automatically
set during autotuning.
0.00 to
650.00
0.40
*4
No
Q
Q
Q
Q
Q
318H
6-115
Mtr Rated
Power
E2-12
Motor iron
saturation
coefficient 3
Sets the motor iron saturation
coefficient at 130% of mag-
netic flux.
This constant is automatically
set during autotuning.
1.30 to
1.60
1.30
No
No
No
A
A
A
328H
6-118
Saturation
Comp3
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2