5
-22
* The setting range for acceleration/deceleration times depends on the setting of C1-10 (Acceleration/deceleration Time Setting Unit). If C1-10 is set to 0,
the setting range is 0.00 to 600.00 (s).
S-curve Acceleration/Deceleration: C2
User constants for S-curve characteristics are shown in the following table.
C1-10
Accel/decel
time setting
unit
0: 0.01-second units
1: 0.1-second units
0 or 1
1
No
A
A
A
A
A
209H
4-21
6-18
Acc/Dec
Units
C1-11
Accel/decel
time switch-
ing fre-
quency
Sets the frequency for auto-
matic acceleration/decelera-
tion switching.
Below set frequency: Accel/
decel time 4
Above set frequency: Accel/
decel time 1
The multi-function input
“accel/decel time 1” or
“accel/decel time 2” take pri-
ority.
0.0 to
400.0
0.0 Hz
No
A
A
A
A
A
20AH
4-21
6-19
Acc/Dec SW
Freq
Con-
stant
Num-
ber
Name
Description
Setting
Range
Fac-
tory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
C2-01
S-curve
characteris-
tic time at
accelera-
tion start
All sections of the S-curve characteris-
tic time are set in seconds units.
When the S-curve characteristic time is
set, the accel/decel times will increase
by only half of the S-curve characteris-
tic times at start and end.
0.00 to
2.50
0.20 s
No
A
A
A
A
A
20BH
4-21
6-19
SCrv Acc
@ Start
C2-02
S-curve
characteris-
tic time at
accelera-
tion end
0.00 to
2.50
0.20 s
No
A
A
A
A
A
20CH
4-21
6-19
SCrv Acc
@ End
C2-03
S-curve
characteris-
tic time at
decelera-
tion start
0.00 to
2.50
0.20 s
No
A
A
A
A
A
20DH
4-21
6-19
SCrv Dec
@ Start
C2-04
S-curve
characteris-
tic time at
decelera-
tion end
0.00 to
2.50
0.00 s
No
A
A
A
A
A
20EH
4-21
6-19
SCrv Dec
@ End
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
Run Command
Output
frequency
Time
ON
OFF
C2-02
C2-03
C2-04
C2-01