Conformance to UL Standard
10-
11
10
Conformance to UL Standard
To comply with UL standard, follow the appropriate installation instructions.
Installation Site
Install the Inverter in a pollution degree 2 environment or equivalent.
Specification of Closed-Loop Connector
The closed-loop connectors must be installed on conductors before installing to terminal blocks.
Use UL Listed closed-loop connectors shown below.
Table 10.2 JST Closed-Loop Connector Model
Inverter
Model CIMR-G7A
JST Kit P/N
Input
Output
27P5
14-5
14-5
2015
38-8
38-8
2018
60-8
38-8
2022
60-8
60-8
2030
80-10
80-10
2037
100-10
100-10
2045
60-10 (2perPh)
60-10 (2perPh)
2055
80-12 (2perPh)
80-10 (2perPh)
2075
150-12 (2perPh)
100-12 (2perPh)
2090
150-12 (2perPh)
150-12 (2perPh)
2110
200-12 (2perPh)
150-12 (2perPh)
4011
8-5
8-5
4015
14-5
14-5
4018
14-6
14-6
4022
22-6
22-6
4030
38-8
22-8
4037
38-8
38-8
4045
60-8
60-8