Appendix
12 - 16
Table 12.1
User Constants (Continued)
No.
Name
(Display)
Factory
Setting
Setting
No.
Name
(Display)
Factory
Setting
Setting
C2-03
S-curve characteristic time at deceleration start
(SCrv Dec @ Srat)
0.20
d1-03
Frequency reference 3
(Reference 3)
0.00
C2-04
S-curve characteristic time at deceleration end
(SCrv Dec @ End)
0
d1-04
Frequency reference 4
(Reference 4)
0.00
C3-01
Slip compensation gain
(Slip Comp Gain)
1.0
:
1
d1-05
Frequency reference 5
(Reference 5)
0.00
C3-02
Slip compensation primary delay time
(Slip Comp Time)
200
:
1
d1-06
Frequency reference 6
(Reference 6)
0.00
C3-03
Slip compensation limit
(Slip Comp Limit)
200
d1-07
Frequency reference 7
(Reference 7)
0.00
C3-04
Slip compensation during regeneration
(Slip Comp Regen)
0
d1-08
Frequency reference 8
(Reference 8)
0.00
C3-05
Flux calculation method
(Flux Select)
0
d1-09
Jog frequency reference
(Jog Reference)
6.00
C3-06
Output voltage limited operation selection
(Output V Limit)
0
d2-01
Frequency reference upper limit
(Ref Upper Limit)
100.0
C4-01
Torque compensation gain
(Torq Comp Gain)
1.00
d2-02
Frequency reference lower limit
(Ref Lower Limit)
0.0
C4-02
Torque compensation time constant
(Torq Comp Time)
20
:
1
d3-01
Jump frequency 1
(Jump Freq 1)
0.0
C4-03
Start torque compensation (forward direction)
(F TorqCmp@ Start)
0.0
d3-02
Jump frequency 2
(Jump Freq 2)
0.0
C4-04
Start torque compensation (reverse direction)
(R TorqCmp@ Start)
0.0
d3-03
Jump frequency 3
(Jump Freq 3)
0.0
C4-05
Start torque time constant
(TorqCmp Delay T)
10
d3-04
Jump frequency width
(Jump Bandwidth)
1.0
C5-01
ASR proportional (P) gain 1
(ASR P Gain 1)
20.00
:
1
d4-01
Frequency reference hold function selection
(MOP Ref Memory)
0
C5-02
ASR integral (I) time 1
(ASR I Time 1)
0.500
:
1
d4-02
+
−
Speed limits
:
2
(Trim Control Lvl)
25
C5-03
ASR proportional (P) gain 2
(ASR P Gain 2)
20.00
:
1
d5-01
Torque control selection
(Torq Control Sel)
0
C5-04
ASR integral (I) time 2
(ASR I Time 2)
0.500
:
1
d5-02
Torque reference delay time
(Torq Ref Filter)
0
C5-05
ASR limit
(ASR Limit)
5.0
d5-03
Speed limit selection
(Speed Limit Sel)
1
C5-06
ASR primary delay time
(ASR Delay Time)
0.004
d5-04
Speed limit
(Speed Lmt Value)
0
C5-07
ASR switching frequency
(ASR Gain SW Freq)
0.0
d5-05
Speed limit bias
(Speed Lmt Bias)
10
C5-08
ASR integral (I) limit
:
2
(ASR I Limit)
400
d5-06
Speed/torque control switching timer
(Ref Hold Time)
0
C6-01
Carrier frequency upper limit
(Carrier Freq Max)
15.0
:
3
E1-01
Input voltage setting
(Input Voltage)
200
:
4
C6-02
Carrier frequency lower limit
(Carrier Freq Min)
15.0
:
3
E1-02
Motor selection
(Motor Selection)
0
C6-03
Carrier frequency proportional gain
(Carrier Freq Gain)
0
:
3
E1-03
V/f pattern selection
(V/F Selection)
0F
C7-01
Hunting prevention selection
(Hunt Prev Select)
1
E1-04
Max. output frequency
(Max Frequency)
60.0
C7-02
Hunting prevention gain
(Hunt Prev Gain)
1.00
E1-05
Max. voltage
(Max Voltage)
200.0
:
4
C8-08
AFR gain
(AFR Gain)
1.00
E1-06
Base frequency
(Base Frequency)
60.0
C8-09
Speed feedback detection control (AFR) time
:
2
(AFR Time)
50
E1-07
Mid. output frequency
(Mid. Frequency A)
3.0
:
1
C8-30
Carrier frequency during autotuning
:
2
(Carrier in tune)
2
E1-08
Mid. output frequency voltage
(Mid Voltage A)
11.0
:
1
:
4
d1-01
Frequency reference 1
(Reference 1)
0.00
E1-09
Min. output frequency
(Min Frequency)
0.5
:
1
d1-02
Frequency reference 2
(Reference 2)
0.00
E1-10
Min. output frequency voltage
(Min Voltage)
2.0
:
1
:
4
* 1. Factory setting depends on the control method (A1-02).
* 2. Not displayed for some models depending on software version No.
* 3. Setting unit and initial setting depend on Inverter capacity.
* 4. Setting for 200 V class Inverters. For 400 V class Inverters, double the value.
12