![YASKAWA VARISPEED-616G5 Instruction Manual Download Page 277](http://html2.mh-extra.com/html/yaskawa/varispeed-616g5/varispeed-616g5_instruction-manual_3217100277.webp)
8.2 Programming Mode Constants
8 - 23
J
Motor 2 Setup: E5
C
Name
S
Change
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
E5 01
Motor 2 rated current
Sets the motor rated current in 1 A
units.
:
These set values will become
the reference values for motor
t ti
t
li it
d
0.32 to
6 40
1.90
×
A
A
A
A
7 7
E5-01
Motor 2 rated FLA
protection, torque limits and
torque control.
These values will automatically
be set if they were set during
autotuning.
6.40
*2
1.90
*1
×
A
A
A
A
7 - 7
E5 02
Motor 2 rated slip
Sets the motor rated slip in Hz
units.
:
These set values will become
th
f
l
f
li
0.00 to
2.90
×
A
A
A
A
7 7
E5-02
Motor 2 Slip Freq
the reference values for slip
compensation.
These values will be automati-
cally set during autotuning.
0.00 to
20.00
2.90
*1
×
A
A
A
A
7 - 7
E5-03
Motor 2 no-load cur-
rent
Sets the motor no-load current in
1 A units.
:
Th
l
ill b
t
ti
*3
1.20
*1
×
A
A
A
A
7 - 7
E5 03
Motor 2 No-load 1
:
These values will be automati-
cally set during autotuning.
*1
×
A
A
A
A
7 7
E5-04
Motor 2 number of
poles
Sets the number of motor poles.
:
These values will automatically
2 to 48
4
×
×
A
×
A
---
E5 04
Motor 2 # Poles
:
These values will automatically
be set during autotuning.
2 to 48
4
×
×
A
×
A
E5-05
Motor 2 line-to-line
resistance
Sets the motor phase-to-phase re-
sistance in
Ω
units.
:
Th
l
ill b
t
ti
0.000 to
65 000
9.842
*1
×
A
A
A
A
7 - 7
E5 05
Motor 2 term Ohms
:
These values will be automati-
cally set during autotuning.
65.000
*1
×
A
A
A
A
7 7
E5-06
Motor 2 leak induc-
tance
Sets the voltage drop due to motor
leakage inductance as a percent-
age of the motor rated voltage.
0.0 to
40 0
18.2
*1
×
×
×
A
A
7 - 8
E5 06
Motor 2 Leak
g
g
:
These values will be automati-
cally set during autotuning.
40.0
*1
×
×
×
A
A
7 8
* 1. The factory setting depends upon the Inverter capacity. The values for a 200 V class Inverter of 0.4 kW will be displayed. See
page 8 - 47.
* 2. The setting range is 10% to 200% of the Inverter’s rated output current. The values for a 200 V class Inverter of 0.4 kW will
be displayed.
* 3. The setting range is 0.00 A to the motor’s rated current
−
0.1 A.
8