User Constants
8.2.6 Terminal Constants: H
8 - 32
H3-05 and H3-09 Settings
S
Control Methods
Setting
Value
Function
Contents
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
0
H3-05: Auxiliary frequency
reference
Maximum output frequency
f
f
f
f
−
0
H3-09: “0” cannot be set
Maximum output frequency
f
f
f
f
1
Frequency gain
Frequency reference (voltage)
command value
f
f
f
f
−
2
Frequency bias (0 limit when
the rotation direction changes.)
* Cannot be set at the same
time as D below (OPE07 will
be displayed.)
Maximum output frequency
(added to H3-03)
f
f
f
f
−
4
Voltage bias
Motor rated voltage (E1-05)
f
f
×
×
−
5
Accel/decel change (reduction
coefficient)
Set acceleration and decelera-
tion times (C1-01 to C1-08)
f
f
f
f
7 - 81
6
DC injection braking current
Inverter rated output current
f
f
f
×
7 - 43
7
Overtorque detection level
Motor rated torque
f
f
f
f
7 - 93
8
Stall prevention level during
run
Inverter rated current
f
f
×
×
7 - 90
9
Frequency reference lower limit
level
Maximum output frequency
f
f
f
f
7 - 57
A
Jump frequency
Maximum output frequency
f
f
f
f
7 - 57
B
PID feedback
Maximum output frequency
f
f
f
f
7 - 46
C
PID target value
Maximum output frequency
f
f
f
f
7 - 46
D
Frequency bias
* Cannot be set at the same
time as 2 above (OPE07 will be
displayed.)
Maximum output frequency
(added to H3-03)
f
f
f
f
−
10
Forward torque limit
Motor’s rated torque
×
×
f
f
7 - 4
7 - 30
11
Reverse torque limit
Motor’s rated torque
×
×
f
f
7 - 4
7 - 30
12
Regeneration torque limit
Motor’s rated torque
×
×
f
f
7 - 4
7 - 30
13
Torque reference/torque limit at
speed control
Motor’s rated torque
×
×
×
f
7 - 27
14
Torque compensation
Motor’s rated torque
×
×
×
f
7 - 25
15
Forward/reverse side torque
limit
Motor’s rated torque
×
×
f
f
7 - 4
7 - 30
H3-05: Not used (terminal 14:
frequency reference)
−
1F
H3-09: Frequency reference
For details, refer to
12.6 Func-
tion Block Diagram
.
Maximum output frequency
f
f
f
f
12 - 20