Basic Operation
6.5.4 Speed Control (ASR) Structure
6 - 44
D
Settings
Setting
Function
0
Deceleration to stop using deceleration time 1 (C1-02).
1
Coast to stop
2
Emergency stop using the emergency-stop time (C1-09).
3
Continue operation (Display “DEV” and continue control.)
4
Deceleration t to stop using deceler action time 1 ( c1
−
02)*2
5
Coast to stop *2
6
Emergency stop using the emergency
−
stop time (c1
−
09)*2
7
Continue Operation (Displays ”DEV” and continues control )*2
* 1. Speed agreement conditions: The frequency reference and output frequency were entered
in the speed agree detection width set in L4
−
02.
* 2. Speed agreement conditions: The frequency reference and the (actual) motor speed based
on the PG feedback value were entered in the speed agree detection width set in L4
−
02.
D
F1-10 and F1-11 Settings
Constant F1-10 sets the PG speed deviation detection level as a percentage of the maximum output
frequency. Constant F1-11 sets the length of time in seconds that the difference between the motor
speed and reference speed must exceed the PG speed deviation detection level in order to detect a PG
speed deviation (DEV).
6.5.4 Speed Control (ASR) Structure
D
The following block diagram shows the structure of the speed control.
Change
limiter
Output fre-
quency
Frequency
reference
−
C5-01, C5-03
P
I
+
+
C5-02, C5-04
C5-05
Detected
speed
+
+
+
Limiter
Fig
6.21
Speed Control Structure
J
Gain Settings
D
When using “V/f control with PG feedback,” set the gain at the minimum output frequency and maxi-
mum output frequency.
Max. Output Frequency Gain Settings: C5-01, C5-02
D
Set the proportional gain (C5-01) and the integral time (C5-02) of the speed control (ASR).
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
C5-01
ASR proportional
(P) gain 1
f
0.00 to
300.00
Mul-
tiple
0.20
×
B
×
B
C5-02
ASR integral (I)
time 1
f
0.000
to10.000
s
0.200
×
B
×
B
Min. Output Frequency Gain Settings: C5-03, C5-04
D
Set ASR proportional gain 2 (C5-03) and ASR integral time 2 (C5-04) for the minimum output fre-
quency.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
C5-03
ASR proportional
(P) gain 2
f
0.00 to
300.00
Mul-
tiple
0.02
×
B
×
B
C5-04
ASR integral (I)
time 2
f
0.000 to
10.000
s
0.050
×
B
×
B
6