User Constants
8.2.6 Terminal Constants: H
8 - 34
Constant
Number
Page
Control Methods
Change
during
Opera-
tion
Factory
Setting
Setting
Range
Description
Name
Constant
Number
Page
Flux
Vector
Open
Loop
Vector
V/f
with
PG
V/f
Change
during
Opera-
tion
Factory
Setting
Setting
Range
Description
Display
H5-03
Communication parity
selection
Set the parity for 6CN MEMO-
BUS communications.
0: No parity
0 to 2
0
×
A
A
A
A
−−
H5 03
Serial Com Sel
0: No parity
1: Even parity
2: Odd parity
0 to 2
0
×
A
A
A
A
H5-04
Stopping method af-
ter communication er-
ror
Set the stopping method for com-
munications errors.
0: Deceleration stop
1: Coast to stop
0 to 3
3
×
A
A
A
A
−−
Serial Fault Sel
1: Coast to stop
2: Emergency stop
3: Continue operation
H5-05
Communication error
detection selection
Set whether or not a communica-
tions timeout is to be detected as a
communications error.
0, 1
1
×
A
A
A
A
−−
H5 05
Serial Flt Dtct
0: Do not detect.
1: Detect
0, 1
1
×
A
A
A
A
8