User Constants
8.2.6 Terminal Constants: H
8 - 28
8.2.6 Terminal Constants: H
J
Multi-function Inputs: H1
C
S
Change
Control Methods
Constant
Number
Name
Display
Setting
Range
Factory
Setting
Change
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
H1-01
Multi-function input 1
(terminal 3)
Terminal 3 Sel
0 to 77
24
×
B
B
B
B
7 - 65
H1-02
Multi-function input 2
(terminal 4)
Terminal 4 Sel
0 to 77
14
×
B
B
B
B
7 - 65
H1-03
Multi-function input 3
(terminal 5)
Terminal 5 Sel
0 to 77
3 (0) *
×
B
B
B
B
7 - 65
H1-04
Multi-function input 4
(terminal 6)
Terminal 6 Sel
0 to 77
4 (3) *
×
B
B
B
B
7 - 65
H1-05
Multi-function input 5
(terminal 7)
Terminal 7 Sel
0 to 77
6 (4) *
×
B
B
B
B
7 - 65
H1-06
Multi-function input 6
(terminal 8)
Terminal 8 Sel
0 to 77
8 (6) *
×
B
B
B
B
7 - 65
* The values in parentheses indicate initial values when initialized in 3-wire sequence.
Multi-function Input Functions
Control Methods
Setting
Value
Function
V/f
V/f
w/
PG
Open
loop
Vector
Flux
vector
Page
0
3-wire sequence (Forward/Reverse run command)
f
f
f
f
6 - 14
1
Local/Remote selection (ON: Operator, OFF: Constant setting)
f
f
f
f
7 - 65
2
Option/Inverter selection (ON: Option card)
f
f
f
f
7 - 65
3
Multi-step speed reference 1
When H3-05 is set to “0,” this function is combined with “Master/auxiliary speed switch.”
f
f
f
f
6 - 14
4
Multi-step speed reference 2
f
f
f
f
6 - 14
5
Multi-step speed reference 3
f
f
f
f
6 - 14
6
Jog frequency reference (higher priority than multi-step speed reference)
f
f
f
f
6 - 14
7
Accel/Decel time 1
f
f
f
f
6 - 17
8
External baseblock NO (NO contact: Baseblock at ON)
f
f
f
f
7 - 66
9
External baseblock NC (NC contact: Baseblock at OFF)
f
f
f
f
7 - 66
A
Accel/Decel ramp hold (ON: Accel/decel stopped, frequency on hold)
f
f
f
f
7 - 66
B
OH2 alarm signal input (ON: OH2 will be displayed)
f
f
f
f
7 - 67
C
Multi-function analog input selection (ON: Enable)
f
f
f
f
7 - 67
D
No V/f control with PG (ON: Speed feedback control disabled,) (normal V/f control)
×
f
×
×
7 - 67
E
Speed control integral reset (ON: Integral control disabled)
×
f
×
f
7 - 67
F
Not used (Set when the terminals are not used)
−
−
−
−
−
10
Up command (Always set with the down command)
f
f
f
f
7 - 68
11
Down command (Always set with the up command)
f
f
f
f
7 - 68
12
FJOG command (ON: Forward run at jog frequency d1-09)
f
f
f
f
6 - 17
13
RJOG command (ON: Reverse run at jog frequency d1-09)
f
f
f
f
6 - 17
14
Fault reset (Reset when turned ON)
f
f
f
f
7 - 69
15
Emergency stop. (Normally open condition: Deceleration to stop in emergency stop time
C1-09 when ON.)
f
f
f
f
6 - 17
16
Motor switch command (Motor 2 selection)
f
−
f
−
7 - 69
17
Emergency stop (Normally closed condition: Deceleration to stop in emergency stop time
C1-09 when OFF)
f
−
f
−
7 - 69
18
Timer function input (Functions are set with b4-01, b4-02 and the timer function is set at the
same time)
f
f
f
f
7 - 45
19
PID control disable (ON: PID control disabled)
f
f
f
f
7 - 70
8