6.3 V/f Control
6 - 25
V/f Patterns: 55 to 300 kW
D
Fixed Torque Characteristics (Settings 0 to 3)
Setting 0
50 Hz
Setting 1
60 Hz
Setting 2
60 Hz
Setting 3
72 Hz
(V)
200
12
6
0 1.3 2.5
50 (Hz)
(V)
200
12
6
0 1.5 3
60 (Hz)
(V)
200
12
6
0 1.5 3
60 (Hz)
50
(V)
200
12
6
0 1.5 3
60
(Hz)
72
D
Variable Torque Characteristics (Settings 4 to 7)
Setting 4
50 Hz
Setting 5
50 Hz
Setting 6
60 Hz
Setting 7
60 Hz
(V)
200
35
5
0 1.3
25
50 (Hz)
(V)
200
50
6
0 1.3
25
50 (Hz)
(V)
200
35
5
0 1.5
30
60 (Hz)
(V)
200
50
6
0 1.5
30
60 (Hz)
D
High Starting Torque Characteristics (Settings 8 to b)
Setting 8
50 Hz
Setting 9
50 Hz
Setting A
60 Hz
Setting B
60 Hz
(V)
200
15
7
0 1.3 2.5
50 (Hz)
(V)
200
20
9
0 1.3 2.5
50 (Hz)
(V)
200
15
7
0 1.5 3
60 (Hz)
(V)
200
20
11
0 1.5 3
60 (Hz)
D
High-speed Operation (Settings C to E)
Setting C
90 Hz
Setting D
120 Hz
Setting E
180 Hz
(V)
200
12
6
0 1.5 3
60
(Hz)
90
(V)
200
12
6
0 1.5 3
60
(Hz)
120
(V)
200
12
6
0 1.5 3
60
(Hz)
180
The voltages above are for 200 V class Inverters. Double the voltages for 400 V class Inverters.