Connect the AC (L1, L2, L3, N) cables to the terminal block and use the OT
type terminal to connect the ground cable to the internal grounding stud inside the
wiring box. (see the 2
nd
graph in Figure 2.27) Set up the cables referring to Figure 2.29.
Pre-insulated end ferrule
3pcs
Pre-insulated end ferrule
Core wire
OT type terminal
Core wire
OT type terminal,1pcs
Figure 2.31 - AC Output and Ground Cable Set Up
(
2
)
Connect the AC (L1, L2, L3, N) cables to the terminal block and use the OT
type terminal to connect the ground cable to the external grounding point at the
bottom of the wiring box. (see the 3
rd
graph in Figure 3-27 ) Set up the cables referring
to Figure 2.30.
Pre-insulated end ferrule
3pcs
Pre-insulated end ferrule
Core wire
OT type terminal,2pcs
Ground wire
Figure 2.31 - AC Output and Ground Cable Set Up
INSTRUCTION:
The attached pre-insulated end ferrules match with the #6AWG
cables. If
a different gauge is selected, a different pre-insulated end ferrule will
need to be provided by the installers.