Snap the CT onto the conductor.
Connect CTs to the correspondingly colored voltage leads. If the application can
exceed 20 times the rated CT current, use wire ties to secure the I-bar to the CT
housing.
This CT automatically detects phase reversal, so CT load orientation is not
important.
Figure 2.47 - Use wire ties to secure the I-bar to the CT housing.
4.
Connect the shielded twisted pair Modbus cable to the Modbus (RS-485) terminal
as shown in Figure 2.44. Only add a 120 ohm termination resistor if the RGM is the
last Modbus device in the Modbus daisy chain.
Do not connect the cable shield to the RGM.
5.
Enable power for the RGM and the SolrenView Logger will automatically discover
the RGM when it is turned on.