PVI 36TL Installation and Operation Manual (Rev H)
DOCR-070588-H
Page
92
of
120
(a) (b)
Figure 5.2 - Default Indication Interface for Normal Operation
In this mode, the inverter converts the power generated by PV modules to AC
continuously and feeds into the power grid.
(3) Standby mode, as shown in Figure 6-3:
The inverter will enter standby mode when the output voltage and power of PV
modules do not meet the startup conditions or PV voltage and input power are lower
than the set values. The inverter will check automatically whether it meets the startup
conditions in this mode until it turns back to normal mode. The inverter will switch
from standby mode to fault mode if a malfunction occurs.
Standby
>>>>>>
Figure 5.3 - Inverter System in Standby Mode
(4) Fault mode, as shown in Figure5.-4:
The inverter will disconnect from the power grid and turn into fault mode when
the inverter or power grid fails. Check the specific cause in “Troubleshooting table”
(Table 6.2) according to the fault message displayed on the LCD and eliminate the
fault referring to the instructions.