PVI 36TL Installation and Operation Manual (Rev H)
DOCR-070588-H
Page
91
of
120
5.0: Operation
5.1 Start-up
Manual Start-up
: Manual start-up is required after regulation setting or manual
(fault) shut-down. Move the cursor from the main operation interface to “4 Setting”.
Press
ENT
and go to submenu “1 ON/OFF”. Then move the cursor to “ON” and press
ENT
to start the inverter. Then the inverter will start up and operate normally if the
start-up conditions are met. Otherwise, the inverter will go to stand-by mode.
Automatic Start-up
: The inverter will start up automatically when the output
voltage and power of PV arrays meet the set values, AC power grid is normal, and the
ambient temperature is within allowable operating range.
5.2 Shutdown
Manual Shutdown
: Normally, it is not necessary to shut down the inverter, but it
can be shut down manually if regulation setting or maintenance is required.
Move the cursor from the main operation interface to “4 Setting”. Press
ENT
and
go to submenu “1 ON/OFF”. Move the cursor to “OFF” and press
ENT
, and then the
inverter will be shut down.
Automatic Shutdown
: The inverter will be shut down automatically when the
output voltage and power of PV modules are lower than the set values, or AC power
grid fails; or the ambient temperature exceeds the normal range.
5.3 Operation Mode
There are 4 operation modes. The following are corresponding indications for
each mode.
(1) System check mode for startup, as shown in Figure 5.1:
Sys.Checking
>>>>>>
Figure 5.1 - System Self-Check Ongoing
This mode indicates that the inverter is checking whether it is ready for normal
operation after the manual start-up of inverter.
(2) Normal operation mode: Default indication interface for normal operation is
shown in Figure 5.2 (a) and 5.2 (b). The switching time between (a) and (b) is 5
seconds.