IMPORTANT: The cable shield should only be connected to ground (GND) at the third
party DAS. Do not connect the shield to any of the inverters
Figure 2.37
Notice how the cable shield is daisy chained together and not landed inside the inverter.
S402 is in the OFF position, or down towards the P208 connector when the inverter is in
the middle of the daisy chain.
Warning:
Risk of Electric Shock.
Make sure all shield wires are properly secured and insulated to prevent shorting to
any other components inside the inverter.
6.
Close the wiring box.
7.
Reconnect AC and DC power and turn the inverter on when it is safe.
8.
Configure the Inverter Modbus ID and Baud rate using the front LCD display.