Internal protection of the inverter
Possible causes:
Protection procedure occurs inside the inverter
Recommended solutions:
1.Observe for 10 minutes and see whether the alarm
will be eliminated automatically;
2.Contact after-sales service personnel
Fault
IntFault0010~0150
Definition:
Internal fault of the inverter
Possible causes:
Fault occurs inside the inverter
Recommended solutions:
1.The inverter can be forced to restart once if it is
required by operation and if it is confirmed that there
is no other problem;
2.Contact after-sales service personnel
6.2 Product Maintenance
6.2.1 Check the Electrical Connection
Check all the cable connections as a regular maintenance inspection every 6
months or once a year.
1.) Check the cable connections. If loose, please tighten all the cables referring to
“2.3 Electrical Installation”.
2.) Check for cable damage, especially whether the cable surface is scratched or
smooth. Repair or replace the cables if necessary.
INSTRUCTION:
*The actual display of “PV.VoltOver” is “PV1VoltOver” or “PV2VoltOver”.
*The actual display of “PV.Reverse” is “PV1Reverse” or “PV2Reverse”.
DANGER:
Please disconnect the inverter from AC grid and PV modules before
opening the equipment. Make sure hazardous high voltage and energy
inside the equipment has been discharged.
Do not operate or maintain the inverter until at least 5 minutes after
disconnecting all sources of DC and AC.