Figure 4.17 - Q(U) Curve Mode
The Table 5-5 lists the parameters of QReactSet, PF Set, PF(P) Curve and Q(U) Curve
modes. Press
ENT
to start up the modes after the parameters are set up.
Table 4.5 - Parameters of Reactive Power Control (IEEE-1547)
Mode
Parameter Name
Setup range (lower limit,
default & upper limit)
Description
Q
ReactiveComp(%)
(-60.0%, 0.0%, 60.0%)
PF
PowerFactor
(-0.80, 1.000, 0.80)
PF(P)
PFCurveP1(%)
(0, 50.0%, 100.0%)
See Figure 5-17
PFCurvePF1
(-0.800, 1.000, 0.800)
See Figure 5-17
PFCurveP2(%)
(0, 100.0%, 100.0%)
See Figure 5-17
PFCurvePF2
(-0.800, -0.900, 0.800)
See Figure 5-17
PFCurvTripV(V)
(480.0, 480.0, 528.0)
PF curve trip voltage
PFCurveReV(V)
(422.4, 432.0, 480.0)
PF curve revocation
voltage
Q(U)
QuCurveU1(V)
(480.0, 518.4, 528.0)
See Figure 5-18
QuCurveQ1(%)
(-100.0%, 0.0%, 100.0%)
See Figure 5-18
QuCurveU2(V)
(480.0, 528.0, 528.0)
See Figure 5-18
Capacitive
Q(%)
_
+
Inductive
(QuCurveU2i,QuCurveQ2i)
U(V)
(QuCurveU1i,
QuCurveQ1i)
(QuCurveU1,
QuCurveQ1)
(QuCurveU2,QuCurveQ2)