4.6 Setup Procedure for Elevator Applications
94
YASKAWA EUROPE SIEP
YASKAWA AC Drive L1000V Technical Manual
n
Rescue Operation Torque Limit
The Torque Limit During Rescue Operation is set in parameter S4-05. After Rescue Operation is complete, the drive
utilizes to the torque limits set in the L7 parameters.
n
Light Load Direction Search Function
Light Load Direction Search can be used to automatically perform Rescue Operation in the direction with the lower load.
It can help to minimize the amount of power required by the backup power supply required for Rescue Operation. Light
Load Direction Search can be set so that it is automatically performed when Rescue Operation is started. To enable Light
Load Direction Search set parameter S4-01 = 1.
When Light Load Direction Search is enabled the drive first runs in the up and then in the down direction, each for the
time set to S4-03. It then compares the load condition of both operations and travels to the next floor using the lighter
load condition direction. The speed reference used for Light Load Direction Search can be set in parameter S4-04.
• When the lightest load direction is up, the drive stops after Light Load Direction Search and then accelerates upwards
to the Rescue Operation speed set in parameter d1-25. The output terminals set for “Light Load Direction” (H2-
=
54) and “Light Load Direction detection status”(H2-
= 55) will close.
Figure 4.14
Figure 4.15 Light Load Direction Detection (Up)
• When the lightest direction is down, then after Light Load Direction Detection is finished the drive immediately
accelerates to the Rescue Operation speed set in d1-25 without stopping. An output terminal set for “Light load
direction” (H2-
= 54) will stay open, and an output terminal set for “Light Load Direction detection status”(H2-
= 55) will close.
Figure 4.15
Figure 4.16 Light Load Direction Detection (Down)
H1-
غغ
= 55
(Rescue Operation)
Up
Off (open)
Off (open)
Up
Down
Speed agree torque calculations
Elevator moves in the
direction of the light load
Up/Down command
Up command (internal)
Down command (internal)
On (closed)
On (closed)
㧔
Light Load Direction Search status
㧕
H2-
= 55
㧔
Light load direction
㧕
H2-
= 54
Off (open)
Off (open)
On (closed)
On (closed)
H1-
غغ
= 55
(Rescue Operation)
Up
Off (open)
Off (open)
Down
Speed agree torque calculations
Elevator moves in the
direction of the light load
Up/Down command
Up command (internal)
Down command (internal)
On (closed)
On (closed)
㧔
Light Load Direction Search status
㧕
H2-
= 55
㧔
Light load direction
㧕
H2-
= 54
Off (open)
Off (open)
On (closed)
Summary of Contents for Lift Inverter L1000V
Page 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...