5.7 H: Terminal Functions
YASKAWA EUROPE
SIEP
YASKAWA AC Drive L1000V Technical Manual
133
5
Setting 2F: Maintenance period
Output closes when the cooling fan, DC bus capacitors, or DC bus pre-charge relay may require maintenance as
determined by the estimated performance life span of those components.
Component performance life is displayed as a
percentage on the digital operator screen. Refer to
Periodic Maintenance on page 195
for details.
Setting 30: During torque limit
Output closes when the motor is operating at the torque limit specified by the L7-
parameters or an analog input.
This setting can only be used in OLV, CLV and CLV/PM control modes. Refer to
L7-01 to L7-04: Torque Limits on
for details.
Setting 37: During frequency output
Output closes when the drive is outputting a frequency.
Figure 5.22
Figure 5.22 During Frequency Output Time Chart
Setting 50: Brake control
This setting can be used in the brake sequence for the elevator application. Closing the output terminal should cause the
brake to release, and opening the terminal should apply the brake. Refer to
for details.
Setting 51: Output contactor control
Assigning this command to an output terminal can send a signal to the controller to close the output contactor. The output
contactor should open when the terminal is released.
Setting 54: Light load direction
Indicates the light load direction detected during emergency operation with light load search. When the terminal is closed
the light load direction is up, when it is open the light load direction is down. Refer to
Setting 55: Light load direction detection status
This terminal is open during Light Load Direction Search. When the search function is complete, the terminal closes.
Refer to
Light Load Direction Search Function on page 94
for details.
Setting 58: Safe disable status
This terminal closes if the Safe Disable inputs H1-HC are closed and opens when terminals H1-HC are open.
Note:
This digital output function is only available on L1000V drives with firmware version 7011 and later.
Setting 100 to 158: Functions 0 to 58 with Inverse Output
These settings have the same function as settings 0 to 58 but with inverse output. Set as 1
, where the “1” indicates
inverse output and the last two digits specify the setting number of the function.
Examples:
• For inverse output of “8: During baseblock”, set 108.
Status
Description
Open
Drive is stopped or one of the following functions is being performed: baseblock, DC Injection Braking, Short Circuit Braking.
Closed
Drive is outputting frequency.
ON
ON
OFF
OFF
ON
OFF
ON
Up/Down command
Baseblock
command
Output
frequency
During run
During frequency
Output
OFF
common̲
TMonly
Summary of Contents for Lift Inverter L1000V
Page 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...