3.7 Control Circuit Wiring
YASKAWA EUROPE
SIEP
YASKAWA AC Drive L1000V Technical Manual
57
3
NOTICE: Separate wiring for digital output terminals MA, MB, MC and M1 to M6 from wiring to other control circuit lines. Improper
wiring practices could result in drive or equipment malfunction or nuisance trips.
NOTICE: Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2, W/T3, -, +1, +2) and
other high-power lines. Improper wiring practices could result in drive malfunction due to electrical interference.
NOTICE: Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper application of peripheral
devices could result in drive performance degradation due to improper power supply.
NOTICE: Do not exceed 50 meters (164 feet ) for the control line between the drive and the operator when using an analog signal from
a remote source to supply the frequency reference. Failure to comply could result in poor system performance.
NOTICE: Do not use unshielded cable for control wiring. Failure to comply may cause electrical interference resulting in poor system
performance. Use shielded, twisted-pair wires, and ground the shield to the ground terminal of the drive.
Wire the control circuit only after terminals have been properly grounded and main circuit wiring is complete. Refer to
for details. Prepare the ends of the control circuit wiring as shown in
. Refer to
.
NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in drive or
equipment malfunction due to electrical interference.
Connect control wires as shown in
:
Figure 3.15
Figure 3.14 Terminal Board Wiring Guide
To disconnect control wires from the terminals use the procedure described in
. Grasp the wire where it
enters the terminal with a pair of pliers, then use a straight-edge screw driver to release the terminal and pull the wire out.
If it fits tightly, e.g. if ferrules are used, turn the wire for about 45
°
and then pull it gently out. Use this procedure to
remove the wire jumper between terminals HC and H1 that is preinstalled at shipping.
Figure 3.16
Figure 3.15 Removing Wires from the Terminal Board
Terminal Board
Control Wires
Push wire end
into terminal
YEG
Terminal Board
Control Wires
Push down to open
the terminal
Turn the wire ~ 45
and pull it out of the
terminal.
Use a screwdriver with a blade
width of max 2.5 mm and a
thickness of max 0.4 mm
45
Y E
Summary of Contents for Lift Inverter L1000V
Page 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...