868
YASKAWA ELECTRIC
SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
■
2: External Reference 1/2 Selection
Setting
Function
Description
2
External Reference 1/
2 Selection
Sets the drive to use Run command source 1/2 or Reference command source 1/2 when in
REMOTE Mode.
Note:
When the drive is receiving a Run command, you cannot switch between reference sources.
ON :
b1-15 = [Frequency Reference Selection 2], b1-16 [Run Command Selection 2]
OFF :
b1-01 = [Frequency Reference Selection 1], b1-02 [Run Command Selection 1]
■
3: Multi-Step Speed Reference 1
Setting
Function
Description
3
Multi-Step Speed
Reference 1
Uses speed references
d1-01 to d1-08 [Multi-Step Speed Reference]
to set a multi-step speed
reference.
Note:
Refer to
“
Setting Procedures for Multi-step Speed Operation
”
in
“
d: Reference Settings
”
for more information.
■
4: Multi-Step Speed Reference 2
Setting
Function
Description
4
Multi-Step Speed
Reference 2
Uses speed references
d1-01 to d1-08 [Multi-Step Speed Reference]
to set a multi-step speed
reference.
Note:
Refer to
“
Setting Procedures for Multi-step Speed Operation
”
in
“
d: Reference Settings
”
for more information.
■
5: Multi-Step Speed Reference 3
Setting
Function
Description
5
Multi-Step Speed
Reference 3
Uses speed references
d1-01 to d1-08 [Multi-Step Speed Reference]
to set a multi-step speed
reference.
Note:
Refer to
“
Setting Procedures for Multi-step Speed Operation
”
in
“
d: Reference Settings
”
for more information.
■
6: Jog Reference Selection
Setting
Function
Description
6
Jog Reference
Selection
Sets the drive to use the JOG Frequency Reference (JOG command) set in
d1-17
. The JOG
Frequency Reference (JOG command) overrides Frequency References 1 to 16 (d1-01 to d1-16).
■
7: Accel/Decel Time Selection 1
Setting
Function
Description
7
Accel/Decel Time
Selection 1
Sets the drive to use
Acceleration/Deceleration Time 1 [C1-01, C1-02]
or
Acceleration/
Deceleration Time 2 [C1-03, C1-04]
.
Note:
Refer to
“
C1: Accel & Decel Time
”
for more information.
■
8: Baseblock Command (N.O.)
Setting
Function
Description
8
Baseblock Command
(N.O.)
Sets the command that stops drive output and coasts the motor to stop when the input is ON.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV