YASKAWA ELECTRIC
SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
263
Model
Terminals
Recommended
Gauge
AWG, kcmil
Applicable
Gauge
(IP20
Applicable
Gauge
)
AWG, kcmil
Wire
Stripping
Length
mm
Terminal Screw
Tightening
Torque
N
∙
m (lb
∙
in.)
Size
Shape
2313
R/L1, S/L2, T/L3
4/0 × 2P
3 - 4/0 × 2P
(2/0 - 4/0 × 2P)
-
M10
Hex self-locking nut
20
(177)
U/T1, V/T2, W/T3
3/0 × 2P
3 - 4/0 × 2P
(2/0 - 4/0 × 2P)
-
M10
Hex self-locking nut
20
(177)
-, +1
250 × 2P
2 - 250 × 2P
(4/0 - 250 × 2P)
-
M10
Hex self-locking nut
20
(177)
+3
1/0 × 2P
4 - 1/0 × 2P
(1/0 × 2P)
-
M10
Hex self-locking nut
20
(177)
2
2 - 350
(-)
-
M10
Hex bolt (slotted)
18 - 23
(159 - 204)
2360
R/L1, S/L2, T/L3
250 × 2P
2/0 - 300 × 2P
(250 - 300 × 2P)
-
M12
Hex self-locking nut
35
(310)
U/T1, V/T2, W/T3
250 × 2P
2/0 - 300 × 2P
(250 - 300 × 2P)
-
M12
Hex self-locking nut
35
(310)
-, +1
350 × 2P
4/0 - 400 × 2P
(300 - 400 × 2P)
-
M12
Hex self-locking nut
35
(310)
+3
3/0 × 2P
1/0 - 4/0 × 2P
(-)
-
M12
Hex self-locking nut
35
(310)
1
1 - 350
(-)
-
M12
Hex bolt (slotted)
32 - 40
(283 - 354)
2415
R/L1, S/L2, T/L3
250 × 2P
2/0 - 300 × 2P
(250 - 300 × 2P)
-
M12
Hex self-locking nut
35
(310)
U/T1, V/T2, W/T3
300 × 2P
2/0 - 300 × 2P
(250 - 300 × 2P)
-
M12
Hex self-locking nut
35
(310)
-, +1
350 × 2P
4/0 - 400 × 2P
(300 - 400 × 2P)
-
M12
Hex self-locking nut
35
(310)
+3
3/0 × 2P
1/0 - 4/0 × 2P
(-)
-
M12
Hex self-locking nut
35
(310)
1
1 - 350
(-)
-
M12
Hex bolt (slotted)
32 - 40
(283 - 354)
*1
For IP20 protection, use wires that are in the range of applicable gauges.
*2
Remove insulation from the ends of wires to expose the length of wire shown.
*3
For wire gauges more than AWG 8, tighten to a tightening torque of 4.1 N∙m to 4.5 N∙m (36 lb∙in. to 40 lb∙in.).
*4
Terminals - and +1 have two screws. The Recommended Gauge is the wire gauge for one terminal.
*5