YASKAWA ELECTRIC
SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
549
Setting
Function
Description
Ref.
1E
Reference Sample
Hold
Sets the command to sample the frequency reference at terminals A1, A2, or A3 and hold
the frequency reference at that frequency.
20 to 2F
External Fault
Sets a command to stop the drive when a failure or fault occurs on an external device.
20 : External Fault (NO-Always-Ramp)
21 : External Fault (NC-Always-Ramp)
22 : External Fault (NO-@Run-Ramp)
23 : External Fault (NC-@Run-Ramp)
24 : External Fault (NO-Always-Coast)
25 : External Fault (NC-Always-Coast)
26 : External Fault (NO-@Run-Coast)
27 : External Fault (NC-@Run-Coast)
28 : External Fault (NO-Always-FStop)
29 : External Fault (NC-Always-FStop)
2A : External Fault (NO-@Run-FStop)
2B : External Fault (NC-@Run-FStop)
2C : External Fault (NO-Always-Alarm)
2D : External Fault (NC-Always-Alarm)
2E : External Fault (NO-@Run-Alarm)
2F : External Fault (NC-@Run-Alarm)
30
PID Integrator
Reset
Sets the command to reset and hold the PID control integral to 0 when the terminal is
ON.
31
PID Integrator
Hold
Sets the command to hold the integral value of the PID control while the terminal is
activated.
32
Multi-Step Speed
Reference 4
Sets the command to switch
d1-09 to d1-16 [Reference 9 to 16]
with multi-step speed
references 1, 2 and 3.
34
PID Soft Starter
Disable
Sets the PID soft starter function.
ON : Disabled
OFF : Enabled
35
PID Input (Error)
Invert
Sets the command to turn the terminal ON and OFF to switch the PID input level
(polarity).
3E
PID Setpoint
Selection 1
Set this function and
H1-xx = 3F [PID Setpoint Selection 2]
together. Sets the function to
switch the PID setpoint to
b5-58 to b5-60 [PID Setpoint 2 to 4]
.
3F
PID Setpoint
Selection 2
Set this function and
H1-xx = 3E [PID Setpoint Selection 1]
together. Sets the function to
switch the PID setpoint to
b5-58 to b5-60 [PID Setpoint 2 to 4]
.
40
Forward RUN (2-
Wire)
Sets the Forward Run command for 2-wire sequence 1. Set this function and
H1-xx = 41
[Reverse Run Command (2-Wire Seq)]
together.
ON : Forward Run
OFF : Run Stop
Note:
•
Turning ON the Forward Run command terminal and the Reverse Run command
terminal will cause alarm
EF [FWD/REV Run Command Input Error]
and the motor
will ramp to stop.
•
Initialize the drive with a 2-wire sequence to set the Forward Run command to
terminal S1.
•
This function will not operate at the same time as
H1-xx = 42, 43 [Run Command/
FWD/REV Command (2-Wire Seq 2)]
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV