YASKAWA ELECTRIC
SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
989
This calibration function lets the drive suppress the torque ripple of a motor. Usually it is not necessary to change
this setting.
0 : No Calibration
1 : One Time Calibrate at Next Start
2 : Calibrate Every Time at Start
■
n1-16: Hunting Prevention High Fc Gain
No.
(Hex.)
Name
Description
Default
(Range)
n1-16
(0BFB)
Hunting Prevention
High Fc Gain
Sets the gain for the hunting prevention function. This parameter functions
best with a high carrier frequency. Usually it is not necessary to change this
setting.
Determined by o2-04
(0.00 - 2.50)
Set
n1-01 = 2 [Hunting Prevention Selection = Enabled (High Carrier Frequency)]
to enable this function.
If the motor oscillates, set
n1-01 = 2
. If that does not have an effect, increase this parameter in 0.2-unit
increments.
■
n1-17: Hunting Prevent High Fc Filter
No.
(Hex.)
Name
Description
Default
(Range)
n1-17
(0BFC)
Expert
Hunting Prevent High
Fc Filter
Sets the responsiveness of the hunting prevention function. Usually it is not
necessary to change this setting.
500 ms
(0 - 1000 ms)
When
n1-01 = 2 [Hunting Prevention Selection = Enabled (High Carrier Frequency)]
, if the motor stalls when
the load changes, increase the value set in this parameter in 100 ms increments.
If you set
n1-01 = 2
and you cannot suppress hunting, increase the value set in this parameter in 100 ms
increments.
◆
n2: Auto Freq Regulator (AFR)
The speed feedback detection reduction function (or AFR: Automatic Frequency Regulator) helps the speed
become stable when you suddenly apply or remove a load.
Note:
Before you change
n2-xx parameters
, do one of these procedures:
•
Set the motor parameters and V/f pattern correctly.
•
Do Rotational Auto-Tuning.
■
n2-01: Automatic Freq Regulator Gain
No.
(Hex.)
Name
Description
Default
(Range)
n2-01
(0584)
Automatic Freq
Regulator Gain
Sets the gain of the AFR function as a magnification value. Usually it is not
necessary to change this setting.
1.00
(0.00 - 10.00)
Adjust this parameter in these conditions:
•
If hunting or oscillation occurs with light loads, increase the setting value in 0.05-unit increments and examine
the response.
•
When torque is not sufficient with heavy loads or to make the torque or speed response better, decrease the
setting value in 0.05-unit increments and examine the response.
■
n2-02: Automatic Freq Regulator Time 1
No.
(Hex.)
Name
Description
Default
(Range)
n2-02
(0585)
Automatic Freq
Regulator Time 1
Sets the time constant that sets the rate of change for the AFR function.
Usually it is not necessary to change this setting.
50 ms
(0 - 2000 ms)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV