YASKAWA ELECTRIC
SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
235
Model
Terminals
Recommended
Gauge
mm
2
Applicable
Gauge
(IP20
Applicable
Gauge
)
mm
2
Wire
Stripping
Length
mm
Terminal Screw
Tightening
Torque
N
∙
m (lb.
∙
in.)
Size
Shape
2257
R/L1, S/L2, T/L3
50 × 2P
25 - 95 × 2P
(70 - 95 × 2P)
-
M10
Hex self-locking nut
20
(177)
U/T1, V/T2, W/T3
50 × 2P
25 - 95 × 2P
(70 - 95 × 2P)
-
M10
Hex self-locking nut
20
(177)
-, +1
70 × 2P
35 - 120 × 2P
(120 × 2P)
-
M10
Hex self-locking nut
20
(177)
+3
35 × 2P
25 - 70 × 2P
(70 × 2P)
-
M10
Hex self-locking nut
20
(177)
95
95 - 240
(-)
-
M10
Hex bolt (slotted)
18 - 23
(159 - 204)
2313
R/L1, S/L2, T/L3
70 × 2P
25 - 95 × 2P
(70 - 95 × 2P)
-
M10
Hex self-locking nut
20
(177)
U/T1, V/T2, W/T3
70 × 2P
25 - 95 × 2P
(70 - 95 × 2P)
-
M10
Hex self-locking nut
20
(177)
-, +1
95 × 2P
35 - 120 × 2P
(120 × 2P)
-
M10
Hex self-locking nut
20
(177)
+3
50 × 2P
25 - 70 × 2P
(70 × 2P)
-
M10
Hex self-locking nut
20
(177)
95
95 - 240
(-)
-
M10
Hex bolt (slotted)
18 - 23
(159 - 204)
2360
R/L1, S/L2, T/L3
120 × 2P
70 - 150 × 2P
(150 × 2P)
-
M12
Hex self-locking nut
35
(310)
U/T1, V/T2, W/T3
120 × 2P
70 - 150 × 2P
(150 × 2P)
-
M12
Hex self-locking nut
35
(310)
-, +1
120 × 2P
95 - 185 × 2P
(185 × 2P)
-
M12
Hex self-locking nut
35
(310)
+3
70 × 2P
50 - 95 × 2P
(-)
-
M12
Hex self-locking nut
35
(310)
120
120 - 240
(-)
-
M12
Hex bolt (slotted)
32 - 40
(283 - 354)
2415
R/L1, S/L2, T/L3
120 × 2P
70 - 150 × 2P
(150 × 2P)
-
M12
Hex self-locking nut
35
(310)
U/T1, V/T2, W/T3
120 × 2P
70 - 150 × 2P
(150 × 2P)
-
M12
Hex self-locking nut
35
(310)
-, +1
120 × 2P
95 - 185 × 2P
(185 × 2P)
-
M12
Hex self-locking nut
35
(310)
+3
70 × 2P
50 - 95 × 2P
(-)
-
M12
Hex self-locking nut
35
(310)
120
120 - 240
(-)
-
M12
Hex bolt (slotted)
32 - 40
(283 - 354)
*1
For IP20 protection, use wires that are in the range of applicable gauges.
*2
Remove insulation from the ends of wires to expose the length of wire shown.
*3
For wire gauges more than 30 mm
2
, tighten to a tightening torque of 4.1 N∙m to 4.5 N∙m (36 lb.∙in. to 40 lb.∙in.).
*4
Install an RCM/RCD with this wire gauge to maintain compliance with IEC/EN 61800-5-1:2007.
*5
Terminals - and +1 have two screws. The Recommended Gauge is the wire gauge for one terminal.
*6
A junction terminal is necessary to connect a braking unit (CDBR-series) to terminals - and +3.