Note:
When you use
L7-01 to L7-04
and analog inputs to set torque limits for the same quadrant, it will enable the lower torque limit.
■
13: Torque Reference / Torque Limit
Setting
Function
Description
13
Torque Reference /
Torque Limit
Enters the torque reference if the motor rated torque is 100%. This setting is the torque limit for
speed control.
Note:
When you use
L7-01 to L7-04
and analog inputs to set torque limits for the same quadrant, it will enable the lower torque limit.
■
14: Torque Compensation
Setting
Function
Description
14
Torque
Compensation
Enters the torque compensation value if the motor rated torque is 100%.
■
15: General Torque Limit
Setting
Function
Description
15
General Torque Limit
Enters the torque limit that is the same for all quadrants for forward, reverse, and regenerative
operation if the motor rated torque is 100%.
■
16: Differential PID Feedback
Setting
Function
Description
16
Differential PID
Feedback
Enters the PID differential feedback value if the full scale analog signal (10 V or 20 mA) is 100%.
The drive uses the deviation between the PID feedback and the differential feedback value signals to calculate the
PID input.
■
1F: Not Used
Setting
Function
Description
1F
Not Used
Value for terminals that are not being used or terminals being used in through mode.
When you set a terminal that you do not use to 1F, you can use the signal that is input to that terminal as the PLC
analog signal input from MEMOBUS/Modbus communications or the communication option. This input signal
does not have an effect on drive operation. This signal functions the same as F (Through Mode).
■
30: DWEZ Analog Input 1
Setting
Function
Description
30
DWEZ Analog Input
1
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
■
31: DWEZ Analog Input 2
Setting
Function
Description
31
DWEZ Analog Input
2
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
■
32: DWEZ Analog Input 3
Setting
Function
Description
32
DWEZ Analog Input
3
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV