11 Drive Control and Programming
YASKAWA
TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
73
No.
(Hex.)
Name
Description
H3-14
(041C)
Analog Input Terminal Enable Sel
Sets the enabled terminal or terminals when
H1-xx = C [MFDI Function Select = Analog Terminal Enable Selection]
is
ON.
1 : Terminal A1 only
2 : Terminal A2 only
3 : Terminals A1 and A2
4 : Terminal A3 only
5 : Terminals A1 and A3
6 : Terminals A2 and A3
7 : Terminals A1, A2, and A3
H4-01
(041D)
Terminal FM Analog Output Select
Sets the monitor number to send from MFAO terminal FM.
H4-02
(041E)
RUN
Terminal FM Analog Output Gain
Sets the gain of the monitor signal that is sent from MFAO terminal FM.
H4-03
(041F)
RUN
Terminal FM Analog Output Bias
Sets the bias of the monitor signal that is sent from MFAO terminal FM.
H4-04
(0420)
Terminal AM Analog Output
Select
Sets the monitoring number to be output from the MFAO terminal AM.
H4-05
(0421)
RUN
Terminal AM Analog Output Gain
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
H4-06
(0422)
RUN
Terminal AM Analog Output Bias
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
H4-07
(0423)
Terminal FM Signal Level Select
Sets the MFAO terminal FM output signal level.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
H4-08
(0424)
Terminal AM Signal Level Select
Sets the MFAO terminal AM output signal level.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
L1-01
(0480)
Motor Overload (oL1) Protection
Sets the motor overload protection with electronic thermal protectors.
0 : Disable
1 : Variable Torque
2 : Constant Torque 10:1 Speed Range
3 : Constant Torque 100:1 SpeedRange
4 : PM Variable Torque
5 : PM Constant Torque
6 : Variable Torque (50Hz)
L1-02
(0481)
Motor Overload Protection Time
Sets the operation time for the electronic thermal protector of the drive to prevent damage to the motor. Usually it is not
necessary to change this setting.
L3-04
(0492)
Stall Prevention during Decel
Sets the method that the drive will use to prevent overvoltage faults when decelerating.
0 : Disabled
1 : General Purpose
2 : Intelligent (Ignore Decel Ramp)
4 : Overexcitation/High Flux
5 : Overexcitation/High Flux 2
o1-58
(3125)
Motor Power Unit Selection
Sets the setting unit for parameters that set the motor rated power.
0 : kW
1 : HP
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV