YASKAWA
TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
13
Item
Specification
V/f Characteristics
Select from 15 pre-defined V/f patterns, or a user-set V/f pattern.
Main Control
Functions
Restart After Momentary Power Loss, Speed Search, Overtorque/Undertorque Detection, Torque Limit, 17 Step Speed (max.), Accel/Decel Switch, S-curve
Acceleration/Deceleration, 3-wire Sequence, Auto-Tuning (Rotational and Stationary), Dwell Function, Cooling Fan ON/OFF Switch, Slip Compensation,
Torque Compensation, Jump Frequency, Upper/Lower Limits for Frequency Reference, DC Injection Braking at Start and Stop, Overexcitation Braking, High
Slip Braking, PID Control (with Sleep Function), Energy Saving Control, MEMOBUS/Modbus Communication (RS-485 max. 115.2 kbps), Auto Restart,
Application Presets, KEB, Overexcitation Deceleration, Overvoltage Suppression
Table 5.2 Protection Functions
Item
Specification
Motor Protection
Electronic thermal overload protection
Momentary
Overcurrent
Protection
Drive stops when the output current is more than 175% of the drive rated output current.
Overload Protection
Drive stops when the output current is more than these overload tolerances:
•
110% of the rated output current for 60 seconds
•
140% of the rated output current for 2.5 seconds when the drive output frequency is 3 Hz
The permitted frequency of overload is one time each 10 minutes.
Note:
If output frequency < 6 Hz, the drive can trigger the overload protection function when the output current is in the overload tolerance range.
Overvoltage
Protection
208 V class: Stops when the DC bus voltage is more than approximately 410 V
480 V class: Stops when the DC bus voltage is more than approximately 820 V
Undervoltage
Protection
208 V class: Stops when the DC bus voltage decreases to less than approximately 190 V
480 V class:
•
Stops when the DC bus voltage decreases to less than approximately 350 V when you use an input voltage less than 400 V
•
Stops when the DC bus voltage decreases to less than approximately 380 V when you use an input voltage less than 460 V
•
Stops when the DC bus voltage decreases to less than approximately 440 V when you use an input voltage of 460 V or more
Momentary Power
Loss Ride-thru
Immediately stops when power loss is 15 ms or longer.
Continues operation if power loss is shorter than 2 s (depending on parameter settings).
Note:
Stop time may be shortened depending on the load and motor speed.
Heatsink Overheat
Protection
The drive stops when the thermistor detects an IGBT temperature more than approximately 100 °C (212 °F). The trip temperature level is different for different
drive models.
Stall Prevention
Stall prevention is available during acceleration, deceleration, and during run.
Ground Fault
Protection
Electronic circuit protection
Note:
This protection detects ground faults during run. The drive will not provide protection when:
•
There is a low-resistance ground fault for the motor cable or terminal block
•
Energizing the drive when there is a ground fault.
DC Bus Charge LED
Charge LED illuminates when DC bus voltage is more than 50 V.
Table 5.3 Environment
Item
Specification
Area of Use
Indoors
Power Supply
Overvoltage Category III
Ambient Temperature
Setting
IP20/UL Open Type/Heatsink External Mounting: -10 °C to +50 °C (14 °F to 122 °F)
IP20/UL Type 1: -10 °C to +40 °C (14 °F to 104 °F)
IP55/UL Type 12 Heatsink External Mounting; front side: -10 °C to +50 °C (14 °F to 122 °F)
IP55/UL Type 12 Heatsink External Mounting; back side: -10 °C to +40 °C (14 °F to 104 °F)
•
When you install the drive in an enclosure, use a cooling fan or air conditioner to keep the internal air temperature in the permitted range.
•
Do not let the drive freeze.
•
You can use IP20/UL Open Type and IP20/UL Type 1 drives at a maximum of 60 °C (140 °F) when you derate the output current.
•
You can use IP55/UL Type 12 drives at a maximum of 50 °C (122 °F) when you derate the output current.
Humidity
95% RH or less
Do not let condensation form on the drive.
Storage Temperature
-20 °C to +70 °C (-4 °F to +158 °F) (short-term temperature during transportation)