54
YASKAWA
TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
Note:
•
Energize the drive with factory defaults to show the Initial Setup screen. Push
[Home] to show the HOME screen.
–
Select [No] from the [Show Initial Setup Screen] setting to not display the Initial Setup screen.
•
Push
from the Home screen to show drive monitors.
•
Push
to set
d1-01 [Reference 1]
when the Home screen shows
U1-01 [Frequency Reference]
in LOCAL Mode.
•
The keypad will show [Rdy] when the drive is in Drive Mode. The drive is prepared to accept a Run command.
•
Set
b1-08 [Run Command Select in PRG Mode]
to accept or reject a Run command from an external source while in Programming Mode.
–
Set
b1-08 = 0 [Disregard RUN while Programming]
to reject the Run command from an external source while in Programming Mode
(default).
–
Set
b1-08 = 1 [Accept RUN while Programming]
to accept the Run command from an external source while in Programming Mode.
–
Set
b1-08 = 2 [Allow Programming Only at Stop]
to prevent changes from Drive Mode to Programming Mode while the drive is
operating.
Table 8.2 Drive Mode Screens and Functions
Mode
Keypad Screen
Function
Drive Mode
Monitors
Sets monitor items to display.
Programming Mode
Parameters
Changes parameter settings.
User Custom Parameters
Shows the User Parameters.
Parameter Backup/Restore
Saves parameters to the keypad as backup.
Modified Parameters/Fault Log
Shows modified parameters and fault history.
Auto-Tuning
Auto-Tunes the drive.
Initial Setup Screen
Changes initial settings.
Diagnostic Tools
Sets data logs and backlight.
9
LED Status Ring
The LED Status Ring on the drive cover shows the drive operating status.
A - ALM/ERR
B - Ready
C - RUN