82
YASKAWA
TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
Table 12.3 Required Short Circuit Protection for FP605 AC Drives (480 V Class)
Drive
Catalog
Code
FP65U
Drive Mounted without
Supplemental Enclosure
(Using Type 1 Kit)
Drive Mounted in Supplemental Enclosure
Any Size Protected Enclosure
(Ventilated or Non-Ventilated)
Restricted Size Protected Enclosure
(Ventilated Only)
Semiconductor
Fuse
Part Number
(Permitted Only
in Type 1 Kit)
Manufacturer:
Eaton/Bussmann
Class CC, J, or T
Fuse
Maximum Amps
Semiconductor
Fuse
Part Number
Manufacturer:
Eaton/Bussmann
Class CC, J, or T
Maximum Amps
Class CC, J, or T
Fuse
Maximum Amps
Maximum
Amps
Part Number
Manufacturer:
Schneider
Enclosure Volume
Minimum (in
3
)
External
Heatsink
Internal
Heatsink
4005
Not allowed.
Does not support
internal fuses for
these drive models.
8
FWH‐25A14F
8
Enclosure volume
not restricted.
Refer to the values
in the column to the
left for fuses.
15
HLL36030M71
3056
3056
4006
9
FWH‐30A14F
9
15
HLL36030M71
3056
3056
4008
12
FWH‐30A14F
12
15
HLL36030M71
3056
3056
4011
17.5
FWH‐40B
17.5
25
HLL36030M71
3056
3056
4014
20
FWH‐45B
20
35
HLL36030M71
3056
3056
4021
35
FWH‐60B
35
50
HLL36030M71
3056
3056
4027
45
FWH‐80B
45
60
HLL36050M72
3056
3056
4034
60
FWH‐100B
60
80
HLL36050M72
3056
3056
4040
70
FWH‐125B
70
100
HLL36100M73
5520
5520
4052
90
FWH‐150B
90
125
HLL36100M73
5520
5520
4065
110
FWH‐200B
110
150
HLL36100M73
5520
5520
4077
125
FWH‐225A
125
175
HLL36100M73
5520
5520
4096
150
FWH‐225A
150
225
HLL36150M74
5520
5520
4124
200
FWH‐225A
200
300
JLL36250M75
5520
5520
4156
250
FWH‐325A
250
350
JLL36250M75
21582
14657
4180
300
FWH‐500A
300
450
JLL36250M75
14657
4240
400
FWH‐600A
400
600
LAL3640036M
or
LLL36400M37X
14657
4302
500
FWH‐700A
500
700
LAL3640036M
or
LLL36400M37X
14657
4361
FWH‐800A
Not allowed.
Must use
semiconductor
fuses.
FWH‐800A
Not allowed.
Must use minimum
enclosure volume
requirements.
600
700
PLL34060M68
52800
4414
FWH-1000A
or
FWH-1000B
FWH-1000A
or
FWH-1000B
700
800
PLL34060M68
52800
4477
FWH-1200A
or
FWH-1200B
FWH-1200A
or
FWH-1200B
800
900
PLL34080M68
52800
4515
FWH-1200A
or
FWH-1200B
FWH-1200A
or
FWH-1200B
900
1000
PLL34080M68
52800
4590
FWH-1400A
FWH-1400A
1000
1200
PLL34080M68
52800
4720
FWH-1400A
FWH-1400A
1200
1400
PLL34100M69
52800
*1
Protection device must be in same enclosure with drive.
*2
Class T fuses are fast-acting (non‐time-delay) only. Class CC and J can be either time-delay or non-time-delay.
*3
Protection device and drive permitted in same or separate enclosure.
*4
External heatsink installation on these models requires a heatsink shroud and filter.