Note:
Set
H3-02, H3-10, H3-05 = 0 [Terminal A1 Function Selection, Terminal A2 Function Selection, Terminal A3 Function Selection =
Frequency Reference]
to set A1 to A3 to frequency reference. The drive will add the analog input values together to make the frequency
reference.
■
Set Output Signals for MFAO Terminals FM, AM
Set the signal type for terminals AM and FM to voltage or current output. Use jumper switch S5 and
H4-07, H4-08
[Terminal FM Signal Level Select, Terminal AM Signal Level Select]
to set the signal type.
Figure 10.10 Location of Jumper Switch S5
Terminal
Types of Output Signals
Jumper Switch S5
Parameter
No.
Signal Level
FM
Voltage output
(Default)
H4-07
0: 0 V to 10 V
Current output
2: 4 mA to 20 mA
AM
Voltage output
(Default)
H4-08
0: 0 V to 10 V
Current output
2: 4 mA to 20 mA
■
Switch ON Termination Resistor for MEMOBUS/Modbus Communications
When the drive is the last slave in a MEMOBUS/Modbus communications, set DIP switch S2 to the ON position.
This drive has a built-in termination resistor for the RS-485 interface.
Figure 10.11 Location of DIP Switch S2
Table 10.10 RS-485 Communications Termination Resistor Setting
DIP Switch S2
Description
ON
The built-in termination resistor is ON.
OFF (Default)
The built-in termination resistor is OFF.