12
YASKAWA
TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
Model
Maximum Applicable Motor Output
kW (HP)
Rated Output Current
A
4052
30 (40)
52
4065
37 (50)
65
4077
45 (60)
77
4096
56 (75)
96
4124
75 (100)
124
4156
93 (125)
156
4180
112 (150)
180
4240
150 (200)
240
4302
186 (250)
302
4361
224 (300)
361
4414
261 (350)
414
4477
300 (400)
477
4515
335 (450)
515
4590
375 (500)
590
4720
450 (600)
720
5
Common Drive Specifications
Note:
To get the longest product life, install the drive in an environment that meets the necessary specifications.
Table 5.1 Control Characteristics
Item
Specification
Control Methods
•
V/f Control (V/f)
•
PM Open Loop Vector Control (OLV/PM)
•
EZ Open Loop Vector Control (EZOLV)
Frequency Control
Range
•
EZOLV: 0.01 Hz to 120 Hz
•
V/f and OLV/PM: 0.01 Hz to 400 Hz
Frequency Accuracy
(Temperature
Fluctuation)
Digital inputs: Within ±0.01% of the maximum output frequency (-10 °C to +40 °C (14 °F to 104 °F))
Analog inputs: Within ±0.1% of the maximum output frequency (25 °C ±10 °C (77 °F ±18 °F))
Frequency Setting
Resolution
Digital inputs: 0.01 Hz
Analog inputs: 1/2048 of the maximum output frequency (11-bit)
Output Frequency
Resolution
0.001 Hz
Frequency Setting
Signal
Main speed frequency reference: 0 Vdc to 10 Vdc (20 kΩ), 4 mA to 20 mA (250 Ω), 0 mA to 20 mA (250 Ω)
Main speed reference: Pulse train input (maximum 32 kHz)
Starting Torque
•
V/f: 140%/3 Hz
•
OLV/PM: 100%/10% speed
•
EZOLV: 100%/10% speed
Speed Control Range
•
For Induction Motors:
–
V/f: 1:40
–
EZOLV: 1:10
•
For Permanent Magnet Motors and Synchronous Reluctance Motors:
–
OLV/PM: 1:20
–
EZOLV: 1:10
Torque Limits
Parameter settings allow different limits in four quadrants in EZOLV control method.
Accel/Decel Time
0.0 s to 6000.0 s
The drive can set two pairs of different acceleration and deceleration times.