YASKAWA
TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
79
Model
Terminals
Recommended
Gauge
AWG, kcmil
Ferrule
Crimp Terminal Part Number
Manufacturer: PANDUIT Corp.
Type LCA
Type P
Type S
4302
R/L1, S/L2, T/L3
3/0 × 2
N/A
LCA3/0-12-X
N/A
S3/0-76R-5
or
S3/0-12R-5
U/T1, V/T2, W/T3
3/0 × 2
N/A
LCA3/0-12-X
N/A
S3/0-76R-5
or
S3/0-12R-5
-, +1
4/0 × 2
N/A
LCA4/0-12-X
N/A
S4/0-76R-5
or
S4/0-12R-5
1/0
N/A
LCA1/0-12-X
N/A
S1/0-12R-X
4361
R/L1, S/L2, T/L3
4/0 × 2
N/A
LCA4/0-12-X
N/A
S4/0-12R-5
U/T1, V/T2, W/T3
4/0 × 2
N/A
LCA4/0-12-X
N/A
S4/0-12R-5
-, +1
300 × 2
N/A
LCA300-12-X
N/A
N/A
1/0
N/A
LCA1/0-12-X
N/A
S1/0-12R-X
4414
R/L1, S/L2, T/L3
250 × 2
N/A
LCA250-12-X
N/A
S250-12R-5
U/T1, V/T2, W/T3
300 × 2
N/A
LCA300-12-X
N/A
N/A
-, +1
350 × 2
N/A
LCA350-12-X
N/A
N/A
1/0
N/A
LCA1/0-12-X
N/A
S1/0-12R-X
4477
R/L1, S/L2, T/L3
3/0 × 4
N/A
LCA3/0-12-X
N/A
S3/0-12R-5
U/T1, V/T2, W/T3
3/0 × 4
N/A
LCA3/0-12-X
N/A
S3/0-12R-5
-, +1
4/0 × 4
N/A
LCA4/0-12-X
N/A
S4/0-12R-5
2/0
N/A
LCA2/0-12-X
N/A
S2/0-12R-X
4515
R/L1, S/L2, T/L3
4/0 × 4
N/A
LCA4/0-12-X
N/A
S4/0-12R-5
U/T1, V/T2, W/T3
4/0 × 4
N/A
LCA4/0-12-X
N/A
S4/0-12R-5
-, +1
250 × 4
N/A
LCA250-12-X
N/A
S250-12R-5
2/0
N/A
LCA2/0-12-X
N/A
S2/0-12R-X
4590
R/L1, S/L2, T/L3
4/0 × 4
N/A
LCA4/0-12-X
N/A
S4/0-12R-5
U/T1, V/T2, W/T3
250 × 4
N/A
LCA250-12-X
N/A
S250-12R-5
-, +1
300 × 4
N/A
LCA300-12-X
N/A
N/A
3/0
N/A
LCA3/0-12-X
N/A
S3/0-12R-5
4720
R/L1, S/L2, T/L3
300 × 4
N/A
LCA300-12-X
N/A
N/A
U/T1, V/T2, W/T3
300 × 4
N/A
LCA300-12-X
N/A
N/A
-, +1
400 × 4
N/A
LCA400-12-6
N/A
N/A
4/0
N/A
LCA4/0-12-X
N/A
S4/0-12R-5
*1
Use recommended ferrule or bare wire.
*2
The recommended wire gauge for this part is AWG 2.
◆
Short Circuit Protection Requirements for UL Listing
WARNING
Electrical Shock Hazard. After the input protective device trips, do not immediately energize the drive or operate
peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all indicators are OFF. Then
check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the cause of the problem, contact
Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before you operate the drive or peripheral
devices, it can cause serious injury or death.