YASKAWA
TM.iQp.02 iQpump Drive Programming Manual
63
◆
H2 Digital Outputs
■
Terminal Function Selections
Setting Range:
0 to 42
Factory Defaults: H2-01 = “40: Pump 2 Control”
H2-02 = “41: Pump 3 Control”
The iQpump drive has two multi-function outputs. By programming parameters H2-01 and H2-02, the user can assign specific functions
to each output. Below is a table with a complete list of all of the digital output functions. Because the iQpump drive is a dedicated pump
controller, the digital outputs described in this section only relate to the pump specific functions. Following the table is a more detailed
description of each of the pump related functions.
Table 16 Digital Output Functions
Function: During Run 1 (Setting: 0)
A “During Run 1”output will close whenever the Run command is provided and the iQpump drive is outputting voltage. This will include
deceleration and DC Injection.
Function: Zero Speed (Setting: 1)
The “Zero Speed” output will close whenever the output frequency falls below the Minimum Frequency (E1-09).
Function: Fref/Fout Agree 1 (Setting: 2)
The “Fref/Fout Agree 1” output will close whenever the actual output frequency is within the Speed Agree Width (L4-02) of the current
Speed Command regardless of the direction.
Parameter No.
Parameter Name
H2-01
Terminal M1-M2 Function Selection
H2-02
Terminal M3-M4 Function Selection
Parameter setting
Function
Parameter setting
Function
0
During Run1
11
Reset Cmd Active
1
Zero Speed
12
Timer Output
2
FREF/FOUT Agree 1
17
Torque Detect 1 N.C.
3
FREF/Set Agree 1
1A
Reverse Direction
4
Frequency Detect 1
1E
Restart Enabled
5
Frequency Detect 2
1F
Overload (OL1)
6
Drive Ready
20
OH Pre-alarm
7
DC Bus Undervoltage
28
Drive Enable
8
Baseblock 1
39
Drive Waiting
9
Option Reference
3A
Frequency Reduced, OH
A
Remote Operation
3B
Run from Serial Com
B
Torque Detect 1 N.O.
3D
Cooling Fan Err
C
Loss of Reference
40
Pump 2 Control
E
Fault
41
Pump 3 Control
F
Terminal Not Used
42
Pump Fault
10
Minor Fault
Summary of Contents for CIMR-P7U-2011-107
Page 1: ...iQpump Drive Programming Manual Document Number TM iQp 02 ...
Page 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK ...