Figure 1.31
Figure 31 Custom V/f Pattern Programming Curve
Increasing the voltage in the V/f pattern increases the available motor torque. However, when setting a custom V/f pattern, increase the
voltage gradually while monitoring the motor current, to prevent:
• Drive faults as a result of motor over-excitation
• Motor overheating or excessive vibration
Tables 5 and 6 are for 240 V class units only. For 480 V class units, multiply the voltage values by 2.
Table 5 V/f Pattern Default Settings for Drive Capacity 0.5 to 2 HP for 240 V Class
Table 6 V/f Pattern Default Settings for Drive Capacity 3 to 40 HP for 240 V Class
Parameter
No.
Name
Unit
Factory Setting
E1-03
V/f Pattern Selection
—
0
1
2
3
4
5
6
7
8
9
A
B
C
D
F
E1-04
Max Output Frequency
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0 120.0 60.0
E1-05
Max Output Voltage
V
240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0
E1-06
Base Frequency
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
E1-07
Mid Output Frequency A
V
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
E1-08
Mid Output Voltage A
V
17.2
17.2
17.2
17.2
40.2
57.5
40.2
57.5
21.8
27.6
21.8
27.6
17.2
17.2
17.2
E1-09
Min Output Frequency
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
E1-10
Mid Output Voltage
V
10.3
10.3
10.3
10.3
9.2
10.3
9.2
10.3
12.6
14.9
12.6
17.2
10.3
10.3
10.3
E1-11
Mid Output Frequency B
Hz
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
E1-12
Mid Output Voltage B
V
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
E1-13
Base Voltage
V
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
For 480 V class units, the value is twice that of 240 V class units.
Parameter
No.
Name
Unit
Factory Setting
E1-03
V/f Pattern Selection
—
0
1
2
3
4
5
6
7
8
9
A
B
C
D
F
E1-04
Max. Output Frequency
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0 120.0 60.0
E1-05
Max. Output Voltage
V
240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0
E1-06
Base Frequency
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
E1-07
Mid. Output Frequency A
V
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
E1-08
Mid. Output Voltage A
V
16.1
16.1
16.1
16.1
40.2
57.5
40.2
57.5
20.7
26.4
20.7
26.4
16.1
16.1
16.1
E1-09
Min. Output Frequency
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
E1-10
Mid. Output Voltage
V
8.0
8.0
8.0
8.0
6.9
8.0
6.9
8.0
10.3
12.6
10.3
14.9
8.0
8.0
8.0
E1-11
Mid Output Frequency B
Hz
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
E1-12
Mid Output Voltage B
V
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
E1-13
Base Voltage
V
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
For 480 V class units, the value is twice that of 240 V class units.
Frequency
E1-09 E1-07
E1-06
E1-04
E1-11
Max Voltage E1-05
Mid Voltage B E1-12
Mid Voltage A E1-08
Base Voltage E1-13
Min Voltage E1-10
Min
Freq
Max
Freq
Base
Freq
Mid
Freq
A
Mid
Freq B
Freq A
Summary of Contents for CIMR-P7U-2011-107
Page 1: ...iQpump Drive Programming Manual Document Number TM iQp 02 ...
Page 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK ...