TM.iQp.02 iQpump Drive Programming Manual
■
E1-06 Base Frequency
Setting Range:
0.0 to 120.0 Hz
Factory Default: 60.0 Hz
■
E1-07 Mid Output Frequency A
Setting Range:
0.0 to 120.0 Hz
Factory Default: 3.0 Hz
■
E1-08 Mid Output Voltage A
Setting Ranges: 0.0 to 255.0 V (240 V Models)
0.0 to 510.0 V (480 V Models)
Factory Defaults: 17.2 V (240 V Models)
34.5 V (480 V Models)
■
E1-09 Minimum Output Frequency
Setting Range:
0.0 to 120.0 Hz
Factory Default: 1.5 Hz
■
E1-10 Mid Output Voltage
Setting Ranges: 0.0 to 255.0 V (240 V Models)
0.0 to 510.0 V (480 V Models)
Factory Defaults: 10.3 V (240 V Models)
20.7 V (480 V Models)
■
E1-11 Mid Output Frequency B
Setting Range:
0.0 to 120.0 Hz
Factory Default: 0.0 Hz
■
E1-12 Mid Output Voltage B
Setting Ranges: 0.0 to 255.0 V (240 V Models)
0.0 to 510.0 V (480 V Models)
Factory Defaults: 0.0 V (240 V Models)
0.0 V (480 V Models)
Top set up custom V/f pattern, program the points shown in the diagram below using parameters E1-04 through E1-13. Be sure that the
following condition is true:
E1-09
≤
E1-07
≤
E1-06
≤
E1-11
≤
E1-04
■
E1-13 Base Voltage
Setting Ranges: 0.0 to 255.0 V (240 V Models)
0.0 to 510.0 V (480 V Models)
Factory Defaults: 0.0 V (240 V Models)
0.0 V (480 V Models)
To set up a custom V/f pattern, program the points shown in the diagram below using parameters E1-04 through E1-13. Be sure that the
following condition is true:
E1-09
≤
E1-07
≤
E1-06
≤
E1-11
≤
E1-04
Summary of Contents for CIMR-P7U-2011-107
Page 1: ...iQpump Drive Programming Manual Document Number TM iQp 02 ...
Page 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK ...