92
YASKAWA
TM.iQp.02 iQpump Drive Programming Manual
■
Error Codes
The following table shows Modbus communication error codes.
Table 26 Error Codes
■
Slave Not Responding
In the following cases, the slave will ignore the write function.
• When a communication error (overrun, framing, parity, or CRC-16) is detected in the command message.
• When the slave address in the command message and the slave address in the iQpump drive do not agree.
• When the data that configures the message and the data time length exceed 24 bits.
• When the command message data length is invalid.
Important:
If the slave address specified in the command message is 0, all slaves execute the write function, but do not return response
messages to the master.
Error Code
Contents
01H
Function code error
A function code other than 03H, 08H, or 10H has been set by the PLC.
02H
Invalid register number error
• The register address you are attempting to access is not recorded anywhere.
• With broadcast sending, a start address other than 0000H, 0001H, or 0002H has been set.
03H
Invalid quantity error
• The number of data packets being read or written is outside the range of 1 to 16.
• In write mode, the number of data packets in the message is not No. of packets x 2.
21H
Data setting error
• Upper limit or lower limit error has occurred in the control data or when writing parameters.
• When writing parameters, the parameter setting is invalid.
22H
Write mode error
• Attempting to write parameters to the Drive during run.
• Attempting to write via Enter commands during run.
• Attempting to write parameters other than A1-00 to A1-05, E1-03, or 02-04 when a CPF03 (defective EEPROM) fault has occurred.
• Attempting to write read-only data.
23H
Writing during main circuit undervoltage (UV) fault
• Writing parameters to the Drive during UV (main circuit undervoltage) alarm.
• Writing via Enter commands during UV (main circuit undervoltage) alarm.
24H
Writing error during parameters processing
Attempting to write parameters while processing parameters in the Drive.
Summary of Contents for CIMR-P7U-2011-107
Page 1: ...iQpump Drive Programming Manual Document Number TM iQp 02 ...
Page 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK ...