H1 Digital Inputs
■
Terminal Function Selections
Setting Range:
0 to 86
Factory Defaults: H1-01 = “24: External Fault”
H1-02 = “14: Fault Reset”
H1-03 = “3: Multi-Step SP1” (2-Wire)
“0: 3-Wire Control” (3-Wire)
H1-04 = “80: Hand Mode”
H1-05 = “84: Pre-Charge”
The iQpump drive has five multi-function contact digital inputs. By programming parameters H1-01 through H1-06, the user can assign
specific functions to each input. Below is a table with a complete list of all of the digital input functions. Following the table is a more
detailed description of each of the functions.
Table 8 Digital Input Functions
Parameter No.
Parameter Name
H1-01
Terminal S3 Function Selection
H1-02
Terminal S4 Function Selection
H1-03
Terminal S5 Function Selection
H1-04
Terminal S6 Function Selection
H1-05
Terminal S7 Function Selection
Parameter setting
Function
Parameter setting
Function
0
3-Wire Control
20-2F
External Pump Fault
1
Local/Remote Selection
30
Integral Reset
2
Option/Inv Selection 1
31
Integral Hold
3
Multi-step SP1
34
PI Soft Start Cancel
4
Multi-step SP2
35
PI Input Characteristic
6
Not Used
36
Option/Inv Selection 2
7
Multi-Accel/Decel 1
60
Motor Pre-heat
8
External Baseblock N.O.
61
Speed Search 1
9
External Baseblock N.C.
62
Speed Search 2
A
Accel/Decel Ramp Hold
64
Speed Search 3
C
Terminal A2 Enable
67
Communications Test Mode
F
Terminal Not Used
68
High Slip Braking
10
MOP Increase
6A
Drive Enable
11
MOP Decrease
6B
Comm/Inv Selection
12
Not Used
6C
Com/Inv SEL 2
13
Not Used
6D
Not Used
14
Fault Reset
6E
Not Used
15
Fast Stop N.O.
70
Not Used
17
Fast Stop N.C.
80
Hand Mode
18
Timer Function
81
Disable Sleep Mode
19
PI Disable
82
Sleep Activation
1B
Program Lockout
83
Thermostat Fault
1C
Not Used
84
Disable Pre-Charge
1D
Not Used
85
Low Water Level
1E
Not Used
86
Fixed Speed Auto
Summary of Contents for CIMR-P7U-2011-107
Page 1: ...iQpump Drive Programming Manual Document Number TM iQp 02 ...
Page 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK ...