YASKAWA
TM.iQp.02 iQpump Drive Programming Manual
165
■
P4-05 Thrust Bearing Frequency
Setting Range:
0.0 to 120.0 Hz
Factory Default: 0.0 Hz
The iQpump drive can be configured for special functions for dedicated pumping applications. These functions are: Pre-Charge Level
(P4-01) and Thrust Bearing Frequency (P4-05).
Refer to the Pre-Charge Level (P4-01) for further description about the pre-charge function.
The thrust bearing function will be activated when the frequency value is greater than 0 for the Thrust Bearing Frequency (P4-05)
parameter and the pre-charge function is de-activated. The pre-charge function will de-activate the thrust bearing function.
The thrust bearing frequency of the iQpump drive will operate as determined by programming the Thrust Bearing Frequency (P4-05).
The drive’s output will ramp up or accelerate up to the thrust bearing frequency based on the acceleration time programmed in the Thrust
Bearing Acceleration Time (P4-04).
The PI mode is automatically disabled during the thrust bearing operation. Once the output frequency reaches the thrust bearing
frequency programmed in the Thrust Bearing Frequency (P4-05), the drive will automatically switch to the Auto Mode or automatic
regulation. The thrust bearing function is available in Hand and Auto Modes.
The Thrust Bearing and Pre-Charge functions will work in tandem, if both are enabled.
Setting Thrust Bearing Frequency (P4-05) to a value of 0 will disable this function.
The Thrust Bearing Frequency (P4-05) works in conjunction with the Thrust Bearing Acceleration Time (P4-04).
When the thrust bearing function is activated, a “Thrust Bearing” alarm will be displayed on the digital operator.
Note:
• In Auto Mode, the Minimum Pump Frequency (P1-06) will become the thrust bearing frequency if the minimum pump
frequency is less than the Thrust Bearing Frequency (P4-05).
• In Hand Mode, the minimum frequency will be the Thrust Bearing Frequency (P4-05).
• The thrust bearing function is required when using Electric Submersible Motors. See “CAUTION” statement that follows.
Figure 1.128
Figure 133
CAUTION
The following procedures are necessary for proper protection and setup of a submersible pump, for example
Franklin Electric Submersible Pumps.
The Franklin Electric Submersible Pump (motor) requires an acceleration and deceleration time of one second when
accelerating up from 0 - 30 Hz, or decelerating down from 30 - 0 Hz. The frequency reference of 30 Hz is the minimum
allowable speed of the Franklin Electric motors. Please verify that the pump (motor) running at 30 Hz does not produce
too much pressure for the pump application. Shut-off pressure at 30 Hz is 25% of shut-off pressure at 60 Hz.
TIME
0 Hz
Thrust Freq.
P4-05
Stop
Auto Mode Run Command
Auto Mode Run
PI Enabled, Continue Normal Auto Operation
Acceleration
Time P4-04
PI Disabled
Summary of Contents for CIMR-P7U-2011-107
Page 1: ...iQpump Drive Programming Manual Document Number TM iQp 02 ...
Page 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK ...