176
YASKAWA
TM.iQp.02 iQpump Drive Programming Manual
b5-07
01ABH
PI Offset Adjustment
PI Offset
Sets the amount of offset of the output of the PI controller. Set as a% of
fmax.
The PI Offset Adjustment parameter has two different uses. Parameter
b5-07 serves different functions depending on whether it is used on a
standard PI loop or a Differential PI loop.
1: Parameter b5-07 causes an offset to be applied to the output of the PI
function in a non-Differential PI loop. Every time the PI output is
updated, the offset is summed with the PI output. This can be used to
artificially kick-start a slow starting PI loop.
2: If the Drive is configured for Differential PI Regulation (H3-09=16),
then the PI Offset is the targeted maintained differential between the
signal measured on analog input A1 and the signal measured on analog
input A2.
–100.0 to
+100.0
0.0%
Programming
b5-08
01ACH
PI Primary Delay Time
Constant
PI Delay Tim
e
Sets the amount of time for a filter on the output of the PI controller.
0.00 to
10.00
0.00 sec Programming
b5-09
01ADH
PI Output Level
Selection
Output Level Sel
Determines whether the PI controller will be direct or reverse acting.
0: Normal Output (direct acting)
1: Reverse Output (reverse acting)
0 or 1
0
Programming
b5-10
01AEH
PI Output Gain Setting
Output Gain
Sets the output gain of the PI controller.
0.0 to 25.0
1.0
Programming
b5-12
01B0H
PI Feedback Reference
Missing Detection
Selection
PFb los Det Sel
0: Disabled
1: Alarm
2: Fault
0 to 2
0
Pump Quick
Setup
—
b5-13
01B1H
PI Feedback Loss
Detection Level
Fb los Det Lvl
Sets the PI feedback loss detection level as a percentage of maximum
frequency (E1-04).
0 to 100
0%
Pump Quick
Setup
b5-14
01B2H
PI Feedback Loss
Detection Time
Fb los Det Time
Sets the PI feedback loss detection delay time in terms of seconds.
0.0 to 25.5
1.0 sec
Pump Quick
Setup
b5-17
01B5H
PI Accel/Decel Time
Acc/Dec Time
Applies an accel/decel time to the PI setpoint reference.
0.0 to 25.5
0.0 sec
Programming
Denotes that parameter can be changed when the drive is running.
Energy Saving
b8-01
01CCH
Energy Saving Control
Selection
Energy Save Sel
Energy Savings function enable/disable selection
0: Disabled
1: Enabled
0 or 1
0
Programming
b8-04
01CFH
Energy Saving
Coefficient Value
Energy Save COEF
Used to fine-tune the energy savings function.
0.0 to
655.00
kVA
Dependent
Programming
b8-05
01D0H
Power Detection Filter
Time
kW Filter Time
0 to 2000
20 ms
Programming
b8-06
01D1H
Search Operation Voltage
Limit
Search V Limit
0 to 100
0%
Programming
Accel / Decel
C1-01
0200H
Acceleration Time 1
Accel Time 1
Sets the time to accelerate from zero to maximum frequency.
0.0 to
6000.0
25.0 sec
Pump Quick
Setup
C1-02
0201H
Deceleration Time 1
Decel Time 1
Sets the time to decelerate from maximum frequency to zero.
25.0 sec
Pump Quick
Setup
C1-03
0202H
Acceleration Time 2
Accel Time 2
Sets the time to accelerate from zero to maximum frequency when
selected via a multi-function input.
10.0 sec Programming
C1-04
0203H
Deceleration Time 2
Decel Time 2
Sets the time to decelerate from maximum frequency to zero when
selected via a multi-function input.
10.0 sec Programming
C1-05
0204H
Acceleration Time 3
Accel Time 3
Sets the time to accelerate from zero to maximum frequency when
activated by P3-12. Used for system response stabilization.
50.0 sec Programming
C1-06
0205H
Deceleration Time 3
Decel Time 3
Sets the time to decelerate from maximum frequency to zero when
activated by P3-12. Used for system response stabilization.
50.0 sec Programming
C1-09
0208H
Fast Stop Time
Fast Stop Time
Sets the time to decelerate from maximum frequency to zero for the
“Fast Stop” function.
0.0 to
6000.0
10.0 sec Programming
Denotes that parameter can be changed when the drive is running.
Parameter
No.
Modbus
Address
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page
No.
Summary of Contents for CIMR-P7U-2011-107
Page 1: ...iQpump Drive Programming Manual Document Number TM iQp 02 ...
Page 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK ...