YASKAWA
TM.iQp.02 iQpump Drive Programming Manual
189
L8-12
04B8H
Ambient Temperature
Setting
Ambient Temp
When the Drive is installed in an ambient temperature exceeding its
rating, Drive overload (OL2) protection level is reduced.
45 to 60°C
45°C
Programming
L8-15
04BBH
OL2 Characteristic
Selection at Low Speeds
OL2 Sel @ L-Spd
This parameter assists in protecting the output transistor junctions from
overheating when output current is high and output frequency is low.
0: Disabled
1: Enabled (L8-18 is active)
0 or 1
1
Programming
L8-18
04BEH
Soft CLA Selection
Soft CLA Sel
Enables and disables current limit “A”.
0: Disabled
1: Enabled.
0 or 1
1
Programming
L8-19 04BFH
OH Frequency Reference
Reduction Level
Fref During OH
Sets the amount of frequency reference reduction when an Overheat
Pre-alarm (OH) is detected.
0.0 to
100.0
20.0%
Programming
Hunting Prev
n1-01
0580H
Hunting Prevention
Selection
Hunt Prev Select
0: Disabled (Hunting prevention function disabled.)
1: Enabled (Hunting prevention function enabled.)
If the motor vibrates while lightly loaded, hunting
prevention may reduce the vibration. There is a loss of responsiveness
if hunting prevention is enabled.
0 or 1
1
Programming
n1-02
0581H
Hunting Prevention Gain
Setting
Hunt Prev Gain
Gain setting for the Hunting Prevention Function.
If the motor vibrates while lightly loaded and n1-01=1, increase the
gain by 0.1 until vibration ceases. If the motor stalls while n1-01=1
decrease the gain by 0.1 until the stalling ceases.
0.00 to
2.50
1.00
Programming
High Slip
n3-01
0588H
High-Slip Braking
Deceleration Frequency
Width
HSB Decel Width
Sets how aggressively the Drive decreases the output frequency as it
stops the motor. If overvoltage (OV) faults occur during HSB, this
parameter may need to be increased.
Note:
Function Deactivated
1.0 to 20.0
5%
Programming
n3-02
0589H
High-Slip Braking
Current Limit
HSB Current Ref
Sets the maximum current to be drawn during a HSB stop. Higher n3-
02 settings will shorten motor stopping times but cause increased
motor current, and therefore increased motor heating.
.
Note:
Function Deactivated
100.0 to
200.0
150%
Programming
n3-03
058AH
High-Slip Braking Dwell
Time at Stop
HSB DwelTim@ Stp
Sets the amount of time the Drive will dwell at E1-09 (Minimum
Frequency). If this time is set too low, the machine inertia can cause the
motor to rotate slightly after the HSB stop is complete and Drive
output is shut off.
.
Note:
Function Deactivated
0.00 to
10.0
1.0 sec
Programming
n3-04
058BH
High-Slip Braking
Overload Time
HSB OL Time
Sets the time required for a HSB Overload Fault to occur when the
Drive output frequency does not change for some reason during a HSB
stop. Normally this does not need to be adjusted.
Note:
Function Deactivated
30.0 to
1200.0
40 sec
Programming
Monitor Select
o1-01
0500H
User Monitor Selection
User Monitor Sel
Selects which monitor will be displayed upon power-up when o1-02 =
4.
6 to 94
6
Programming
o1-02
0501H
User Monitor Selection
After Power-Up
Power-On Monitor
Selects which monitor will be displayed upon power-up.
1: Auto: Setpoint
2: Output Freq
3: Output Current
4: User Monitor (set by o1-01)
1 to 4
1**
Programming
o1-05
0504H
LCD Brightness
Adjustment
LCD Contrast
0 to 5
3
Programming
o1-06
0517H
User Monitor Selection
Mode
Monitor Mode Sel
Selects the “U1” monitors displayed on the 4th and 5th lines of the
digital operator display.
0: 3 Mon Sequential (Displays the next 2 sequential U1 monitors.)
1: 3 Mon Selectable (Displays U1 monitors set by o1-07 and o1-08.)
0 or 1
1**
Programming
Denotes that parameter can be changed when the drive is running.
Parameter
No.
Modbus
Address
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page
No.
Set Value
Description
5
LCD display becomes dark
3
Standard setting
1
LCD display becomes light
Summary of Contents for CIMR-P7U-2011-107
Page 1: ...iQpump Drive Programming Manual Document Number TM iQp 02 ...
Page 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK ...