Specifications
14.3.2 Molded Case Circuit Breaker and Magnetic Contactor
1
4
-46
14.3.2 Molded Case Circuit Breaker and Magnetic Contactor
An example of the molded case circuit breaker and magnetic contactor wiring is shown below.
3MCCB
R1
S1
T1
200 VAC
*
R
1MCCB
S
T
3-Phase
Single-phase
1MC
2MCCB
2MC
r
t
R/L1
S/L2
T/L3
A1/r
A2/t
VS-656MR5
To Motor Cooling Fan
Main Circuit Power
Supply Input
Control Power
Supply Input
200 VAC
L
*
: For 400 V Class, 3-phase 400 VAC.
Select MCCB and MC from the table below according to Converter (VS-656MR5) model.
Voltage
Class
Converter
Model
Power
Capacity
MCCB Rated Current (A)
MC Rated Current (A)
Class
Model
CIMR-
MR5
:
Capacity
(kVA)
1MCCB
2MCCB
3MCCB
1MC
2MC
23P7
7
30
3
3
20
3
25P5
9
40
3
3
30
3
27P5
12
50
3
3
40
3
2011
19
75
3
3
60
3
200 V
Class
2015
24
100
3
3
75
3
Class
2018
30
125
3
3
100
3
2022
36
150
3
3
125
3
2030
48
175
3
3
150
3
2037
60
250
3
3
200
3
45P5
9
20
3
2
15
3
47P5
12
25
3
2
20
3
4011
19
40
3
2
30
3
4015
24
50
3
2
40
3
400 V
Class
4018
30
60
3
2
50
3
Class
4022
36
75
3
2
60
3
4030
48
100
3
2
80
3
4037
60
125
3
2
100
3
4045
72
150
3
2
125
3
* A: For stand-alone drive system N: for NC system